6.4. Modbus setup
The METPOINT
FLM thermal flow meter is equipped with a RS 485 interface (Modbus RTU). Before starting the sensor, configure
®
the communication parameters
•
Modbus ID, baud rate, parity and stop bit
to enable communication with the Modbus master.
Setup → ModBus Setup
Default (factory) settings:
Modbus ID:
1
Baud rate:
19200
Stop bit:
1
Parity:
even
Caution:
If the sensor is the last device in the Modbus system, it must be terminated. For details, see chapter „4.5. Modbus termination" auf
Seite 26.
33
Save the settings by pressing the "Save" button.
To apply the default (factory) settings, press the "Set to De-
fault" button.