13.1.1

Error messages

259 Actual Error
Parameter
Actual Error
Error code
Code
F00
00
No fault has occurred.
00
Frequency inverter overloaded, check load behaviour. Reduce ramps and speed.
01
Frequency inverter overloaded in low output frequency range.
F01
02
Frequency inverter overloaded (60 s), check load behaviour.
03
Short-term overload (1 s), check motor and application parameters.
00
Heat sink temperature too high, check cooling and ventilator.
F02
01
Heat sink temperature too cold, check allowed ambient temperature.
00
Inside temperature too high, check cooling and ventilator.
F03
01
Inside temperature too cold, check allowed ambient temperature.
03
Capacitor temperature too high, check cooling and ventilator.
00
Motor temperature too high or sensor defective, check connection at terminal X12.4.
01
Motor circuit breaker tripped, check drive.
F04
02
V-belt monitoring reports no load on the drive.
03
Phase failure, check motor and wiring.
00
Overloaded, check load situation and ramps.
06
Motor phase current too high, check motor and wiring.
07
Message from phase monitoring, check motor and wiring.
08
Message from phase monitoring, check motor and wiring.
F05
09
Message from phase monitoring, check motor and wiring.
Motor still rotates. The motor is still excited and rotates and
− drive start command applies and the flying start function is deactivated or
11
− a device test is tried to start
F06
xx
Internal Error. Please contact your Bonfiglioli office.
00
DC link voltage too high, check deceleration ramps and connected brake resistor.
01
DC link voltage too small, check mains voltage.
02
Power failure, check mains voltage and circuit.
F07
03
Phase failure mains, check mains fuses and circuit.
04
Reference DC-Link Limitation
05
Overvoltage brake chopper. Refer to chapter 13.3 "Troubleshooting" (Shut-down).
Overvoltage motor chopper. Refer to chapter 13.3 "Troubleshooting" (Shut-down).
06
01
Electronics voltage DC 24 V too low, check control terminal.
04
Electronics voltage too high, check wiring of control terminals.
F08
Fault in the the A/D converter. Remove all external connections (signal terminals etc.)
05
and check if the fault remains
Agile
Operating Instructions
259 shows the error code.
Error messages
Overload
Heat Sink
Inside
Motor connection
Output current
Internal Error.
DC–link voltage
680 too small, check mains voltage.
Electronics voltage
06/2013
Meaning
326