Configuration Examples With Simatic S7 Hw-Konfig - Endress+Hauser Proline Promass 80 Operating Instructions Manual

Profibus pa coriolis mass flow measuring system
Hide thumbs Also See for Proline Promass 80:
Table of Contents

Advertisement

Proline Promass 80 PROFIBUS PA
Slot
Module
sequence
1
2
3
4
5
SETTOT_MODETOT_TOTAL
6
DISPLAY_VALUE
7
CONTROL_BLOCK
8
SETTOT_MODETOT_TOTAL
Endress+Hauser
6.6.4

Configuration examples with Simatic S7 HW-Konfig

Example 1:
Fig. 31:
Complete configuration using the Promass 80 GSD file.
It is essential to adhere to the following sequence when configuring the modules in the
PROFIBUS master (Class 1):
Byte length
input data
AI
5
AI
5
AI
5
AI
5
5
5
Byte length
Description
output data
Analog Input function block 1
Output variable  mass flow (factory setting)
Analog Input function block 2
Output variable  volume flow (factory setting)
Analog Input function block 3
Output variable  corrected volume flow (factory setting)
Analog Input function block 4
Output variable  density (factory setting)
Totalizer function block 1
TOTAL  output variable = totalized mass flow (factory setting)
2
SETTOT  totalizer control
MODETOT  totalizer configuration
5
Default value for local display
1
Control of device functions
Totalizer function block 2
TOTAL  output variable = totalized mass flow (factory setting)
2
SETTOT  totalizer control
MODETOT  totalizer configuration
Commissioning
a0004775