User-Programmable Pushbuttons - GE B90 Instruction Manual

Low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

PRODUCT SETUP
Each control pushbutton asserts its own FlexLogic operand. Each operand need to be configured appropriately to perform
the required function. Each operand remains asserted as long as the pushbutton is pressed and resets when the
pushbutton is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton manipulation is recognized
by various features that can use control pushbuttons as inputs.
An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when
the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously—a given key
must be released before the next one can be pressed.

5.3.13 User-programmable pushbuttons

5
SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1(16)
 USER PUSHBUTTON 1
5-98
Figure 5-41: Control pushbutton logic
PUSHBUTTON 1
FUNCTION: Disabled
PUSHBTN 1 ID TEXT:
USER PB 1
PUSHBTN 1 ON TEXT:
PUSHBTN 1 OFF TEXT:
PUSHBTN 1 HOLD:
0.0 s
PUSHBTN 1 SET:
Off
PUSHBTN 1 RESET:
Off
PUSHBTN 1 AUTORST:
Disabled
PUSHBTN 1 AUTORST
DELAY: 1.0 s
PUSHBTN 1 REMOTE:
Off
PUSHBTN 1 LOCAL:
Off
PUSHBTN 1 DROP-OUT
TIME: 0.00 s
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: Self-Reset, Latched, Disabled
Range: up to 20 alphanumeric characters
Range: up to 20 alphanumeric characters
Range: up to 20 alphanumeric characters
Range: 0.0 to 10.0 s in steps of 0.1
Range: FlexLogic operand
Range: FlexLogic operand
Range: Disabled, Enabled
Range: 0.2 to 600.0 s in steps of 0.1
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 60.00 s in steps of 0.05