Setpoints

Hint:
Do not write setpoints repeatedly (e.g. power control from a PLC by repeated writing of baseload
setpoint via Modbus) The setpoints are stored in EEPROM memory, which can be overwritten up to
5
10
times without risk of damage or data loss, but it may become damaged, when the allowed number
of writing cycles is exceeded!

Password

EnterPassword
Password is a four-digit number. Password enables change of relevant protected setpoints.
Use  or  keys to set and ENTER key to enter the password.
Hint:
There is only 1 level of a password.
ChangePassword
Use  or  keys to set and ENTER key to change the password.
Hint:
At first the password has to be entered before the new password can be changed.
During the configuration of controller or setpoints changes is required a password to the
controller. The default password from manufacturer is "0". Maximum value of password is
"9999".
Controller has following functions:
Automatic checking of password during change to be maximally 9999, if it is bigger value it will
be automatically changed to 0. LiteEdit (LE) will prevent to write bigger value than 9999.
Cyclic rotation of value of password in case of using arrows on controller

Basic Settings

Gen-set Name
User defined name, used for InteliLite identification at remote phone or mobile connection.
Gen-set Name is max 14 characters long and have to be entered using LiteEdit software.
Nominal Power
Nominal power of the generator
Step:
1kW
1 – 5000 kW
Range:
Nomin Current
It is current limit for generator *IDMT over current and short current protection and means maximal
continuous generator current. See Gener Protect: *Amps IDMT Del, Short Crct Sd setpoints.
Nominal Current can be different from generator rated current value.
Step:
1 A
Range:
1 - 10000 A
CT Ratio
Gen-set phases current transformers ratio.
NT
– AMF20/25, SW version 2.2, ©ComAp – September 2014
InteliLite
IL-NT-AMF-2.2-Reference Guide.pdf
[kW]
[A]
[/5A]
66