Nibe F1355 Operating Manual page 60

Ground source heat pump
Hide thumbs Also See for NIBE F1355:
Table of Contents

Advertisement

No.
Text in display
323
Flt: EQ1-BT25
350
Sensor fault on
BT50 room sensor.
351
Failed sensor calib-
ration
353
Failed sensor calib-
ration
359
Int temp OPT error
361-
Sensor fault: EPxx-
367
BT3 return line
sensor
369-
Sensor fault: EP12-
370
BT57/BT58
371
Freeze risk EP12-
BT58
420
Inverter alarm type
II
422
Inverter alarm type
II
426
Inverter alarm type
III
60
Chapter 5 |
Disturbances in comfort
Cause
Heat pump action.
The input for the
Calculation of cooling
sensor receives un-
DM performed with
reasonably high or
EQ1-BT25 is set to 0.
low value for longer
than 2 seconds.
The input for the
sensor receives an
unreasonably high or
low value for longer
than 2 seconds when
the sensor is activ-
ated.
Delta BT10-
Change from auto to
BT11>|2K| after calib-
manual brine pump
ration.
speed.
Delta BT3-BT12>|2K|
Change from auto to
after calibration.
manual pump speed.
Alarm from the gas
None.
boiler (GBM).
The input for the
sensor receives un-
reasonably high or
low value for longer
than 2 seconds.
The input for the
None.
sensor receives un-
reasonably high or
low value for longer
than 2 seconds.
Ground water sensor
Blocks operation.
BT58 is below its lim-
it.
A temporary commu-
The compressor is
nication alarm has
stopped.
occurred.
A temporary alarm
The compressor is
on the inverter's ex-
stopped.
ternal input has oc-
curred.
A temporary internal
The compressor is
fault in the inverter
stopped.
has occurred.
Resets automatic-
May be due
ally when
to/check
Open-circuit or
short-circuit on
sensor input.
Defective sensor
Resets automatically
Open-circuit or
when the sensor has
short-circuit on
worked continuously
sensor input.
for 60 seconds.
Defective sensor
Manual.
Manual.
Manual.
Resets automatically
Open-circuit or
when the sensor has
short-circuit on
worked continuously
sensor input.
for 60 seconds.
Defective sensor
Resets automatically
Open-circuit or
when the sensor has
short-circuit on
worked continuously
sensor input.
for 60 seconds.
Defective sensor
Resets automatically
when the temperat-
ure rises above its
limit value +2°C.
Resets automatically
Main and group fuses
60 seconds after rec-
and their cable con-
tified alarm.
nections.
Resets automatically
Main and group fuses
60 seconds after rec-
and their cable con-
tified alarm.
nections.
Resets automatically
Main and group fuses
30 minutes after rec-
and their cable con-
tified alarm.
nections.
Perform a com-
plete restart of the
heat pump. See
page 50.
NIBE F1355