3 The heat pump design General 8 Technical data Electrical cabinets Dimensions and setting-out coordinates Cooling section Technical specifications 4 Pipe connections Energy labelling Electrical wiring diagram, 3x400V 24 - 60 General Dimensions and pipe connections Brine side Index Chapter | NIBE™ F1345...
2006/95/EC, LVD. F1345 is CE marked and fulfils IP21. The appliance is also intended for use The CE marking means that NIBE ensures that the by experts or trained users in shops, product meets all regulations that are placed on it based on relevant EU directives.
Carry out the electrical installation with care. Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line's ground lead. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting. Chapter 1 | Important information NIBE™ F1345...
Improper disposal of the product by the user results in administrative penalties in accordance with current legislation. Country specific information Installer manual This installer manual must be left with the customer. NIBE™ F1345 Chapter 1 | Important information...
NIBE Energy Systems France Sarl, Zone industrielle RD 28, Rue du Pou du Ciel, 01600 Reyrieux Tel : 04 74 00 92 92 Fax : 04 74 00 42 00 E-mail: info@nibe.fr www.nibe.fr NIBE Energy Systems Ltd, 3C Broom Business Park, Bridge Way, Chesterfield S41 9QG Tel: 0845 095 1200 Fax: 0845 095 1201 E-mail: info@nibe.co.uk www.nibe.co.uk...
Before lifting, the heat pump must be separated by pulling the cooling modules out from the cabinet. See the service chapter in the operating manual for instruc- tions about the separation. Chapter 2 | Delivery and handling NIBE™ F1345...
3. Move the hatch outwards and backwards. 4. Assembly takes place in the reverse order. 1. Remove the screws from the lower edge of the front cover. 2. Lift the cover out at the bottom edge and up. NIBE™ F1345 Chapter 2 | Delivery and handling...
F1345 24 kW, 3x400 V AA 10 Soft-start card FC 1 Miniature circuit-breaker BT14 Designations in component locations according to standard IEC 81346-1 and 81346-2. GQ10 BT17 XL21 BT15 EB10 XL20 Chapter 3 | The heat pump design NIBE™ F1345...
Page 13
Condenser GQ 10 Compressor BT14 HS 1 Drying filter QN 1 Expansion valve BT15 Designations in component locations according to BT17 standard IEC 81346-1 and 81346-2. XL20 GQ10 XL21 EB10 BT29 NIBE™ F1345 Chapter 3 | The heat pump design...
Caution Because the temperature of the brine system varies depending on the heat source, the menu 5.1.7 "br pmp al set." must be set to the suit- able value. Chapter 4 | Pipe connections NIBE™ F1345...
Page 17
Volume pressure expansion vessel (l) 800 1000 1200 1400 1600 1800 2000 Total volume refrigerant in system (l) NIBE™ F1345 Chapter 4 | Pipe connections...
1.9.3.1 - min. flow line Desired temperature in the temp. heating tank. 5.1.2 - max flow line temper- Desired temperature in the ature tank. 5.1.10 - op. mod heat med intermittent pump 4.2 - op. mode manual Chapter 4 | Pipe connections NIBE™ F1345...
F1345 can be connected in several different ways, some Miscel- of which are shown below. laneous Further option information is available at www.nibe.eu Accessory card and in the respective assembly instructions for the ac- Manometer, brine side cessories used. See page 39 for a list of the accessories Temperature sensor, hot water flow that can be used with F1345.
Page 20
(EP15) the "temporary lux" function can be used. starts in heat pump (EB101) first. For greater demand, cooling module (EP14) also starts in (EB101) for heating operation. Chapter 4 | Pipe connections NIBE™ F1345...
Electrical installation and wiring must be car- ried out in accordance with the stipulations in force. NOTE Refer to the outline diagram of your system for positioning of the temperature sensor. NIBE™ F1345 Chapter 5 | Electrical connections...
(AUX input) to avoid alarm, see page 29. At the same time external operating voltage for the control system must be connected to the heat pump, see page 23. Chapter 5 | Electrical connections NIBE™ F1345...
Page 23
Connect temperature sensor, external flow (BT25) to terminal block -AA3-X6:5 and -AA3-X6:6. Use a twin core cable of at least 0.5 mm² cable area. F1345 F1345 Externt External -AA3-X6 4 5 6 7 F1345 F1345 Externt External BT25 NIBE™ F1345 Chapter 5 | Electrical connections...
X10:1 (A), -AA101-X10:2 (B) and -AA101-X10:3 (GND), as illustrated. Incoming communications cables from Slave to Slave are connected to terminal block -AA101-X10:4 (A), -AA101-X10:5 (B) and -AA101-X10:6 (GND), as illus- trated. Use cable type LiYY, EKKX or similar. Chapter 5 | Electrical connections NIBE™ F1345...
Page 25
For example, short periods of change combined with under floor heating will not result in a noticeable difference in the -AA101-X10 room temperature. 14 15 16 17 18 19 F1345 F1345 Externt External NIBE™ F1345 Chapter 5 | Electrical connections...
Page 26
AUX input on terminal - 3 to -AA101-X7:1. Connect the neutral from block -AA3-X6 and -AA101-X10. The function must be an external additional heat to -AA101-X5:4 - activated in menu 5.4. Chapter 5 | Electrical connections NIBE™ F1345...
Page 27
Externt External If the relays are to be used for operating voltage, bridge the supply from -AA101-X5:1 - 3 to -AA101-X8:1. Connect the neutral from the external additional heat to -AA101-X5:4 - 6. NIBE™ F1345 Chapter 5 | Electrical connections...
Page 28
QN10 block compressor NIBE Uplink™ activate fan speed 1 Connect the network connected cable (straight, Cat.5e hot water recirc. UTP) with RJ45-contact (male) to contact AA4-X9 on the display unit (as illustrated). Use the cable gland (UB3) in the heat pump for cable routing.
Page 29
■ Switch for external blocking of heating disconnected. Heating is disconnected by connecting a potential free switch function to the input selected in menu 5.4. A closed switch results in blocked heating operation. NIBE™ F1345 Chapter 5 | Electrical connections...
Page 30
Normal speed is resumed when the contact is opened again. ■ Pressure/level/flow monitor brine If a pressure/level/flow monitor brine is required for the brine installation, it can be connected to the se- lected input (menu 5.4). Chapter 5 | Electrical connections NIBE™ F1345...
(230 V AC) in total. Connecting accessories Instructions for connecting accessories are in the install- ation instructions provided for the respective accessory. See page 39 for the list of the accessories that can be used with F1345. NIBE™ F1345 Chapter 5 | Electrical connections...
2. Connect the filling pump and return line on the brine system's service connections as shown in figure. 3. Close the shut-off valve between the service con- nections. 4. Open the service connections. 5. Start the filling pump. Chapter 6 | Commissioning and adjusting NIBE™ F1345...
BT29 is stable 10 degrees greater than sensor BP8 (for F1345-60kW this can take up to 12 hours). See the info menu for more information. NIBE™ F1345 Chapter 6 | Commissioning and adjusting...
Page 35
Electrical output circulation pump, W Tillförd effekt, W Supplied power, W Tillförd eleffekt, W 100% 200,0 100% 180,0 160,0 140,0 120,0 100,0 80,0 60,0 40,0 20,0 Flöde, l/s Flow, l/s Flow, l/s Flöde, l/s NIBE™ F1345 Chapter 6 | Commissioning and adjusting...
Page 36
Set the speed of the heating medium pump in the menu 5.1.11, see the Operating Manual. Read off what speed the heating medium pump should have during manual operation from the diagrams be- low. Chapter 6 | Commissioning and adjusting NIBE™ F1345...
Page 37
Tillförd eleffekt, W 100,0 Eleffekt per cirkulationspump Electrical output per circulation pump, W 90,0 100% 100% 80,0 70,0 60,0 50,0 40,0 30,0 20,0 10,0 Flöde, l/s Flow, l/s Flöde, l/s Flow, l/s NIBE™ F1345 Chapter 6 | Commissioning and adjusting...
Page 38
When the room temperature is too low, increase ■ "heating curve" in menu 1.9.1.1 by one increment. When the room temperature is too high, reduce ■ "heating curve" in menu 1.9.1.1 by one increment. Chapter 6 | Commissioning and adjusting NIBE™ F1345...
GSM module, using a mobile phone via SMS messages. If the mobile telephone also has the Android 26 kW, 3 x 400 V operating system the mobile application ”NIBE Mobile Part no. 067 074 App” can be used.
Page 40
Solar 42 means that F1345 (together with VPAS) can be connected to solar heating. Part no. 067 153 Water heater/Accumulator tank VPA 300/200 Water heater with double-jacketed vessel. Copper Part no. 088 710 Enamel Part no. 088 700 Chapter 7 | Accessories NIBE™ F1345...
2 x 2.0 2 x 1.7 2 x 1.7 Cut-out value pressostat HP 3.2 (32 bar) (42 bar) Difference pressostat HP -0.7 (-7 bar) Cut-out value pressostat LP 0.08 (0.8 bar) (2 bar) Chapter 8 | Technical data NIBE™ F1345...
Page 43
These technical specifications apply to the brine pump supplied for 40 and 60 kW. With feet removed, the height is approx. 1930 mm. NIBE™ F1345 Chapter 8 | Technical data...
Page 44
Returledning Returledning 3x400V 30 kW, 40 kW, 60 kW Vattentemperatur Temperature Vattentemperatur °C °C °C °C Köldbärare in, temperatur Köldbärare in, temperatur Incoming brine temp Framledning Flow pipe Framledning Return pipe Returledning Returledning Chapter 8 | Technical data NIBE™ F1345...
The reported efficiency of the package also takes the controller into account. If an external supplementary boiler or solar heating is added to the package, the overall efficiency of the package should be recalculated. NIBE™ F1345 Chapter 8 | Technical data...
Page 46
0.070 Other items Capacity control Variable Rated airflow (air-water) Sound power level, indoors/outdoors 47 / - Nominal heating medium flow 2.37 Annual energy consumption 15,287 Brine flow brine-water or water-water heat 4.46 pumps Chapter 8 | Technical data NIBE™ F1345...
Page 47
0.070 Other items Capacity control Variable Rated airflow (air-water) Sound power level, indoors/outdoors 47 / - Nominal heating medium flow 3.15 Annual energy consumption 19,880 Brine flow brine-water or water-water heat 5.83 pumps NIBE™ F1345 Chapter 8 | Technical data...
Page 48
0.080 Other items Capacity control Variable Rated airflow (air-water) Sound power level, indoors/outdoors 47 / - Nominal heating medium flow 4.07 Annual energy consumption 25,093 Brine flow brine-water or water-water heat 7.77 pumps Chapter 8 | Technical data NIBE™ F1345...
Page 49
0.080 Other items Capacity control Variable Rated airflow (air-water) Sound power level, indoors/outdoors 47 / - Nominal heating medium flow 5.83 Annual energy consumption 38,048 Brine flow brine-water or water-water heat 10.87 pumps NIBE™ F1345 Chapter 8 | Technical data...
Load monitor, 25 Master/Slave, 24 Marking, 3 Miniature circuit-breaker, 21 Master/Slave, 24 Motor cut-out, 21 Menu system NIBE Uplink™, 28 Help menu, 33 Optional connections, 24 Miniature circuit-breaker, 21 Outdoor sensor, 23 Motor cut-out, 21 Power connection, 22 Resetting, 21...
Page 62
Working range heat pump, 44 Temperature sensor, cooling/heating, 29 Temperature sensor, external flow line, 23–24 Temperature sensor, hot water charging, 23 Temperature sensor, hot water top, 23 The heat pump design, 10 Component list cooling section, 12 Chapter 9 | Item register NIBE™ F1345...
Page 64
WS name: Anders WS version: a5 (working edition) Publish date: 2015-11-03 10:29 NIBE AB Sweden Hannabadsvägen 5 Box 14 SE-285 21 Markaryd info@nibe.se www.nibe.eu 331036...
Need help?
Do you have a question about the F1345 Series and is the answer not in the manual?
Questions and answers