Chapter 2
Basic Operation
2.1
Powering On and Off
2.1.3

Powering On

This section explains how to turn on the ETERNUS DX.
To turn on the ETERNUS DX, perform the following procedure.
Via the power switch
Press the Power switch to turn on the ETERNUS DX.
The following methods can be used to turn the power on by linking with the server.
Power Synchronized Unit
Use the power synchronized unit to turn on the ETERNUS DX.
Wake On LAN
Use the Wake On LAN function to turn on the power.
Before turning on the ETERNUS DX, make sure that the main line switches of the power distribution units
and the PSU switches on the power supply units of the ETERNUS DX are "ON". Do not turn the main line
switches of the power distribution units and the PSU switches on the ETERNUS DX to the OFF position.
After turning on the power of the ETERNUS DX, it takes approximately five minutes (or approximately 10
minutes for a Unified configuration and approximately 20 minutes for a VLAN/Bonding maximum con-
figuration) to be in the READY state (the READY LED turns on). If an error is detected in a component
during the initial power-on diagnostics, it may take a maximum of 10 minutes (or a maximum of 11
minutes for a configuration in which the Deduplication/Compression function is enabled, approximately
40 minutes for a Unified configuration and approximately 50 minutes for a VLAN/Bonding maximum
configuration) for the ETERNUS DX to be in the READY state. If a scheduled operation is being per-
formed, make configurations by taking the operation into consideration.
Before turning the server on, check that the ETERNUS DX and the network devices that connect the
ETERNUS DX and the server are all in READY status.
If the server is turned on while any of these devices are not in READY status, the server may not be able
to recognize the ETERNUS DX.
To turn on the ETERNUS DX by linking with the server, the server must wait until the ETERNUS DX is in
the READY state.
If the Auto Power function is enabled via ETERNUS Web GUI or ETERNUS CLI, the ETERNUS DX is automat-
ically turned on when power is supplied to the ETERNUS DX.
If the Power Resume function is enabled via ETERNUS Web GUI or ETERNUS CLI, the ETERNUS DX is auto-
matically turned on after the power is restored.
After power-off, wait for about one minute before turning power on again.
This section explains how to use the Power switch to turn on the ETERNUS DX.
For other procedures, refer to the related manuals.
FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Operation Guide (Basic)
55
Copyright 2017 FUJITSU LIMITED
P3AM-7662-09ENZ0