6
Operation and troubleshooting
Once the installation and the hydraulic and electrical con-
nections are completed, the ecoLEVEL condensed water
pump is ready for operation. The green LED lights up. The
operation is self-regulating and does not require any fur-
ther manual control.
6.1
LED display of operating status or faults
On the front of the ecoLEVEL condensed water pump cas-
ing, there are two LEDs (¬ fig. 6.1), items 1 and 2) which
indicate the operating status or faults of the ecoLEVEL
condensed water pump.
6.1 Display of operating status
Key
1
Top LED
2 Bottom LED
Which operating status or fault is displayed by the light sig-
nals of the LEDs can be taken from the following table.
ecoLEVEL installation and maintenance instructions 0020029316_01
Operation and troubleshooting
Bottom LED (2) Top LED (1)
Lights up
1
green
Lights up
2
green
3
Flashes green
1
4
Flashes green
5
Flashes green
6.1 Display of operating status
2
6.2
Faults
The ecoLEVEL condensed water pump can automatically
resolve short-term faults in the normal function sequence.
When the maximum permitted water level is reached, both
LEDs flash. If the water level cannot be reduced by pump-
ing, the red LED flashes. As a consequence, the safety cut-
out switch is triggered after approx. 10 seconds. A poten-
tial-free contact or the current circuit opens to switch off
the boiler.
If a corresponding connection to the boiler has been
installed, the boiler is switched off to prevent any further
condensed water from being formed.
6.3
Fault diagnostics and elimination
If the red LED flashes or remains lit for longer than
1 minute, there is a fault in the installation or a defect in
the pump.
> To eliminate this fault, check the following points:
Operating status/Fault
The pump is supplied with
230 V mains voltage. The
-
pump is ready for opera-
tion.
The pump is in operation
Flashes green
and is pumping.
The water level has
exceeded the maximum
permitted value. The
safety cut-out switch is
triggered if this condition
is prolonged.
If a connection between
Lights up red
the safety cut-out switch
and the boiler has been
installed, the boiler is
switched off. Switching off
prevents further con-
densed water from form-
ing.
The pump is at rest for a
defined time period and
Flashes red
then starts up again on its
own.
> Follow the fault diag-
Flashes red
(> 1 min)
nostics (¬ section 6.3)
6
15