GST GST5000 Installation And Operation Manual

GST GST5000 Installation And Operation Manual

Intelligent fire alarm control panel
Table of Contents

Advertisement

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GST5000 and is the answer not in the manual?

Questions and answers

Summary of Contents for GST GST5000

  • Page 2: Table Of Contents

    2.6 Dimension........................ 3 2.6.1 Wall-mounted GST5000W FACP ..............3 2.6.2 Rack type GST5000 FACP ................4 2.6.3 Console type GST5000 control panel ............... 5 Chapter 3 Structure and Configuration ................. 7 3.1 Display and Operation Area..................7 3.1.1 Indicators ......................7 3.1.2 Key Functions ....................
  • Page 3 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 4.4.2 Connection of F.P.E. Output ................21 4.4.3 Connection of Fire Alarm Output..............21 4.4.4 Connection of Class A Loop ................22 4.4.5 Connection of Communication Loop ............... 22 4.4.6 Connection of Ring Module................
  • Page 4 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 6.3.2 Printer Setting ....................44 6.3.3 Security Mode ....................45 6.3.4 Extinguishing Mode..................45 6.3.5 Modification of System Time ................46 6.4 Instructions for System Administrator ..............47 6.4.1 Password Modification ..................
  • Page 5 The Intelligent Solution Preface GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual includes two parties: generic part and Fireman’s Control Panel part. This is the generic part. Please refer to relative part for description on Fireman’s Control Panel.
  • Page 6: Chapter 1 Product Introduction

    The Intelligent Solution Chapter 1 Product Introduction GST5000 Intelligent Fire Alarm Control Panel (FACP) is designed by EN 54-2 standard with qualities of simple installation, operation, and easy maintenance. It is used in fire alarm system with the following features: (1) It controls maximum 60 fire zones.
  • Page 7: Chapter 2 Technical Specifications

    Wiring: Cable length should be less than 15m. 2.4 Detection Loop Parameters LOOP OUT (+, -): Polarized signal bus from GST5000, connecting with 235 addressable devices at most. LOOP IN (+, -): Polarized signal bus returning to GST5000.
  • Page 8: Output Loop Parameters

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Recommended Wiring: GST FireCable ® 2E/1.0 2core and Earth 1mm 2.5 Output Loop Parameters Recommended Wiring: GST FireCable ® 2E/1.0 2core and Earth 1mm (1) FIRE ALARM OUTPUT (+, -) Output Voltage: 21VDC~27VDC...
  • Page 9: Rack Type Gst5000 Facp

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 500mm Display and GST5000 Intelligent Fire Alarm Control Panel operation area Printer CLOCK Zone indication and manual interventional × panel Fireman's control panel Fig. 2-1 2.6.2 Rack type GST5000 FACP...
  • Page 10: Console Type Gst5000 Control Panel

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 580mm Display and operation area GST5000 Intelligent Fire Alarm Control Panel Printer CLOCK × GST64ZCP Zone Indication and Manual Intervention Panel GST64ZCP Zone Indication and Manual Intervention Panel...
  • Page 11 50mm 100mm Fig. 2-3 Note: There are three types of GST5000 FACP: wall-mounted type, rack type and console type. In the following parts of this manual, differences between the three types will be elaborated separately and the similarities described together.
  • Page 12: Chapter 3 Structure And Configuration

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Chapter 3 Structure and Configuration 3.1 Display and Operation Area The display and operation area is shown in Fig. 3-1, which consists of LCD display, indicators, clock display, keypad and printer.
  • Page 13: Key Functions

    ▽ : Page up and down. 3.2 Zone Indication and Manual Intervention Panel (ZCP) The zone indication and manual intervention panels of the three types of GST5000 FACP have the same structure and function. The cabinet of wall-mounted GST5000W FACP can connect with only one GST64ZCP zone indication and manual intervention...
  • Page 14: Structure

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution panel. Rack type and console type can be expanded with more on order. 3.2.1 Structure The ZCP includes two LED boards and one control board. Control board connects with the two LED boards through pins.
  • Page 15: Configuration

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Zone direction mode [ZoneDir] When fire occurs in a zone, corresponding red LED is lit and the sounder strobe is automatically initiated; when fault occurs, corresponding yellow LED flashes; when disabling all devices in the zone, corresponding yellow LED is constantly lit.
  • Page 16 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Fig. 3-4 shows the structure of the motherboard installed on the bottom of the control part. It connects with the AC-DC100W power supply through terminals. There are 4 channel slots for plugging main board, loop card and 232 and 485 communication cards.
  • Page 17 Indicating fire, and fault/disablement of corresponding devices, and starting or stopping them. (2) Typical configurations of GST5000 rack type and console type: Comparing with wall mounted type, the rack and console types can have more loop cards connected to the control cabinet and an intelligent PSU is used.
  • Page 18 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution B: Main board, loop card, communication card Appearances of main board, loop card and communication card are the same as GST5000W wall mounted control panel.
  • Page 19: Optional Configuration

    Fireman’s Control Panel is an important device in the system. These devices include fire pump, smoke exhauster and blower. The FCP of GST5000 intelligent fire alarm control panel can control at most 12 equipments by option. For devices needing both start and stop, it can control at most 6.
  • Page 20: Field Devices

    Note: You need to purchase a CRT card for your first order of GST5000. Only with this CRT card, device definition and C&E equations can be downloaded from PC.
  • Page 21: Addressable Sounder Strobe

    FACP in fire control center or by manual call point installed in field. A series of GST addressable sounder strobes (such as I-9403) can be connected to the bus of GST5000. Having been activated, it will generate strong audible/ visual alarm signal to warn people in field.
  • Page 22: Chapter 4 Mounting

    Installation and Operation Manual (Generic Part) The Intelligent Solution Chapter 4 Mounting Follow the steps before mounting the GST5000: (1) Check whether you have received all items ordered. (2) Mount the cabinet. (3) Power up the FACP and carry out start-up inspection.
  • Page 23: Installation Condition And Method Of Rack Type And Console-Typed Facp

    Installation Space: Width of maintenance of the FACP should be more than 1000mm. 4.3 Start-up Check After mounting GST5000, apply power to it as shown in Fig. 4-2. Turn on the mains and battery switch in the cabinet and check if the FACP can self-test. The procedures are as follows.
  • Page 24: Connections Of Field Devices

    Fail to do so may result in injury! 4.4 Connections of Field Devices Loop interface board combines GST5000 FACP and field devices. Terminals of loop interface board are shown in Fig. 4-3. Fig. 4-3 Description: CLASS CHANGE (XT3): Short it to make the sounders output.
  • Page 25: Connection Of Sounder Circuit Output

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution occurs, and normally open contact is disconnected when the FACP repairs fault automatically. SOUNDER CIRCUIT OUTPUT (XT7): It outputs when there is fire alarm. It can be stopped by pressing SILENCE key on ZCP.
  • Page 26: Connection Of F.p.e. Output

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Diode Diode End-of-line SOUNDER CIRCUIT Resistor 4.7kΩ Sounder OUTPUT (XT7) Sounder Fig. 4-4 Description: A 4.7kΩ resistor is connected at the SOUNDER CIRCUIT OUTPUT as factory default.
  • Page 27: Connection Of Class A Loop

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Diode Diode End-of-line FIRE ALARM Fire Supervisory Resistor 4.7kΩ Fire Supervisory OUTPUT (XT5) Device Device Fig. 4-6 A 4.7kΩ resistor is connected at the FIRE ALARM OUTPUT as factory default. Please remove it and keep it well before connection.
  • Page 28: Connection Of Ring Module

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Network Up to 32 control panels (XT11) 火 灾 Repeater Up to 64 repeater panels 显 (XT12) Fig. 4-8 4.4.6 Connection of Ring Module Loop...
  • Page 29: Definition Of Devices

    System running Fig. 4-11 Step Two: In commission state, re-start the FACP. GST5000 FACP will automatically register devices. Please check the number of devices registered, programming, and operation state comply to design requirement, and remove any problem. 4.6 Definition of Devices Please define devices and C&E equation by configuration software GSTDef2.0 via a PC,...
  • Page 30: Browsing Zone Definition

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution and download the definitions to the FACP. Please refer to GSTDef2.0 Defining Tool User’s Manual for the installation, operation and commission of the software. 4.6.1 Browsing Zone Definition The zone information defined by the definition software can be browsed on the LCD of the FACP following the steps below.
  • Page 31: Browsing Device Information

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution △ = ▽ can be used for turning pages. = 4.6.2 Browsing Device Information The device information defined by the definition software can be browsed on the LCD of the FACP following the steps below.
  • Page 32 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Browse Register info Loop00 000 Repeaters Loop01 000 points 000 Access Browse Register info Loop02 013 points 000 Access Loop00 000 Repeaters Loop03 001 CRT...
  • Page 33: Viewing C&E

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 1 floor cookroom// Zone description + device description №017 Zone 002-017 Fix Temp// Message number, user code (zone number + device number), device type 1 floor bathroom// Zone description + device description №032 Zone 003-032 Optical// Message number, user code (zone number +...
  • Page 34 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Ver V4.05f C&E Formula Browser No000100100103×00100203+00100203×00100303+ 00100103×0100303+00100103×00100203×00100303= 1. General C&E 00100413 00 2. Extinguishing C&E No000200200103×00200203+00200203×00200303+ 00200103×0100303 +00200103×00200203×00200303= 00200513 00 No0003004***03+004***02+004***11=004***1300 Fig. 4-17 Meaning of the above C&E: The part before the "=”...
  • Page 35: Field Devices Commission

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Pressing “3” in Fig. 3-11 can view the spaces for C&Es, as in Fig. 4-18. Ver V4.05f The Space of Equations Used Unused 0011 4789...
  • Page 36: Chapter 5 Display And Disposal Of System Information

    Installation and Operation Manual (Generic Part) The Intelligent Solution Chapter 5 Display and Disposal of System Information GST5000 can be started after mounting according to Chapter 4. 5.1 Normal Information Turn on the external power switch, and main and standby power switch on the FACP, the control panel executes self-test and enters monitoring state.
  • Page 37 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution !Last Fire !16:34 Zone001 6 FLOOR GREEN HOUSE !Fire! total 008 002 16:34 zone 001 1 FLOOR COOKROOM 003 16:34 zone 002 2 FLOOR DINING ROOM...
  • Page 38 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution !Last Fire! 16:34 Zone001 6 FLOOR GREEN HOUSE !Fire! total 100 002 16:34 zone 001-103 OPTICAL 1 FLOOR COOKROOM 003 16:34 zone 001-101 OPTICAL 1 FLOOR DINING ROOM...
  • Page 39: Disposal Of Fire Alarm Signal

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 32 digits) Press Enter to Select an Item //Press ENTER to view a fire alarm message. 5.2.2 Disposal of Fire Alarm Signal When fire alarm occurs, first find out the location according to the information shown on the FACP to verify whether the fire really happened.
  • Page 40: Disposal Of Fault Information

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Description of the fault screen: Each fault message occupies two lines. You can view different fault message by pressing △ = and = ▽ .
  • Page 41 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution DISABLED LED will be lit if the device is disabled. Pressing DISABLE key, the screen will show as in Fig. 5-5. Ver V4.05f System running Disable>...
  • Page 42: Browsing Disabled Information

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Suppose user code of the optical smoke detector to be enabled is 001016. The operation of disablement should be as follows: Step One: Input zone number “001” of the device.
  • Page 43: Manual Start And Stop Of Loop Devices

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 5.5 Manual Start and Stop of Loop Devices When fire alarm is confirmed, you can manually start extinguishing equipment in short time. 5.5.1 START/STOP Operation through Keypad Starting a loop device Pressing START can start a loop device, and the screen is shown in Fig.
  • Page 44: Operation Of The Devices By Zcp

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Ver V4.05f stop> 001zone 016Num 03 -Undefine Fig. 5-9 Basic steps are as follows: Step One: Input the user code of the device to stop.
  • Page 45: Resetting And Silencing Of The System

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution !ACTION! total 100 001 16:34 zone 002-03 OPTICAL 1 FLOOR COOKROOM 002 16:34 zone 002-101 OPTICAL 1 FLOOR DINING ROOM 003 16:34 zone 002-111 OPTICAL...
  • Page 46: Rules For Information Display

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution again or if there are new alarms, the speaker will sound again. 5.7 Rules for Information Display If there are more than one piece of information, they will be displayed in the following order: fire alarm, action, fault, start, disablement.
  • Page 47: Chapter 6 Description Of System Operation

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Chapter 6 Description of System Operation 6.1 Keypad 6.1.1 Functions Most of the keys have double functions. Upper mark is a character and lower mark is command function that is only activated in monitoring state.
  • Page 48: User Operation Instruction

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Ver V4.05f Password 1-8 digits ***** Enter password Fig. 6-1 6.2 User Operation Instruction 6.2.1 Changing time display The clock is usually displayed in hour and minute (time mode) by the digitron on the panel.
  • Page 49: Instructions For System Operator

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution History 12//06//10:45 000000 CRTFault Fault 12//06//10:40 000000 Reset History 12//06//10:37 000000 AC Fault Back 12//06//10:45 000000 CRTFault Fault 12//06//10:28 000000 AC Fault Fault 12//06//10:40 000000 Reset...
  • Page 50: Security Mode

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Pressing △ = and = ▽ followed by ENTER can choose different printing modes: 1. Disable printing 2. Print history records while viewing them 3. Only print fire records 6.3.3 Security Mode...
  • Page 51: Modification Of System Time

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Ver V4.05f Extinguishing System Mode 1. Disable 2. Enable Fig. 6-5 Choosing one from the options can enable or disable gas release function. If it is in Enable mode, the EXTINGUISHING SYSTEM PERMIT indicator will be lit, the gas release device can be started manually or automatically.
  • Page 52: Instructions For System Administrator

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 6.4 Instructions for System Administrator Pressing SYSTEM can enter system setup menu. This menu contains password setting and other functions for commissioning, including "Modify password", "Communicate setup", "Working state setup", "Fire display mode", "Zone browser", "C&E browser"...
  • Page 53 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Ver V4.05f Modify password 1. User Password 2. Extinguishing Password 3. System Password Fig. 6-8 Select the password to be modified, the screen will prompt to enter the old password.
  • Page 54: Communication Setting

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Ver V4.05f Repeat Enter new password ***** Confirm password Fig. 6-10 6.4.2 Communication Setting In system setup menu shown in Fig. 6-7, select the second item “Communicate setup”, you can enter communication setting menu.
  • Page 55: Fire Display Mode

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Ver V4.05f Working state setup 1. Monitoring State 2. Commissioning State Fig. 6-12 Inputting 1, the system enters monitoring state. Inputting 2, the system enters commissioning state.
  • Page 56: Browsing Supervisory Data Of Addressable Devices

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 6.4.7 Browsing supervisory data of addressable devices In the system setup menu as shown in Fig. 6-7, choose item 7 “Monitoring Device”, enter setting mode of fire display, as shown in Fig. 6-14.
  • Page 57: Chapter 7 Commissioning Functions

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Chapter 7 Commissioning Functions The commission mode is set for system commissioning, including registering devices, loop card disablement and detector searching functions. NOTE: Under commission mode, all the registering information will not be saved.
  • Page 58: Exiting Commission Mode

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Restart the control panel in this mode, it will register all devices again. 7.2 Exiting Commission Mode Getting into the screen in Fig. 7-1 and choosing 1 "Monitoring State", the system will exit commission mode.
  • Page 59: Chapter 8 Troubleshooting And Regular Checks

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Chapter 8 Troubleshooting and Regular Checks 8.1 General Fault Treatment Table 1 Fault Reason Solution No display or 1. Abnormal power 1. Check +24 power supply.
  • Page 60: Regular Checks And Replacement

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 8.2 Regular Checks and Replacement The device should be checked regularly: The print paper should be replaced as required prior to running out. Remove Fig. 8-1 Remove the printer front cover as shown in Fig.8-1.
  • Page 61 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Press Press Pull Fig.8-2 3) Remove the scroll spindle (Fig. 8-3). Push Up Fig. 8-3 4) Put the new scroll on the spindle. And press the scroll spindle into the groove of the printer as in Fig.
  • Page 62 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Push down Fig. 8-4 5) Cut the end of the paper according to Fig.8-5. Fig. 8-5 6) Turn on the power of the printer. Press “SEL” key to turn off the “SEL” light. Then press LF to move the head.
  • Page 63 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution paper through the paper slot. 7) Press the printer into the control panel gently. 8) If, according to engineering configuration, the back of the control panel display part is not covered by other structures, it is easier to take the paper from the back.
  • Page 64: Chapter 9 Calculation Of Battery Capacity

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Chapter 9 Calculation of Battery Capacity The equation for calculating battery capacity is as follows: Battery Capacity(Ah)=0.84×T+0.03×N+3.5 In which N is the number of detectors, and T is the time of operation in standby state.
  • Page 65: Appendix 1 Internal Connection Diagram

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Appendix 1 Internal Connection Diagram 1. GST5000W Wall Mounted RJ45 connector to Loudspeaker To RS232 or to router board to RS485 to Loop Card to main board...
  • Page 66 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 2 GST5000 Rack type and console type RJ45 connector Z1n+ Z1n- Z1n+ Z1n- +24V +24V +24V +24V +24V +24V +24V +24V EXTERNAL INTERNAL BAT. BAT.FUSE...
  • Page 67: Appendix 2 Device Type List

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Appendix 2 Device Type List Abbreviation Device type Undefine Undefined Ionization detector R+F.Heat' Rate-of-rise and fixed temperature detector Optical Photoelectrical smoke detector Fix Temp Fixed temperature detector...
  • Page 68 GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution ZoneValv Zone valve Cylinder Cylinder DelugePM Deluge pump Undefine Undefined Stop Mod Device stop Silence Mute key SounderA Fire alarm sounder SounderF Fault sounder Loop SW...
  • Page 69: Appendix 3 Operation Menu

    GST5000 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Appendix 3 Operation Menu Menu MUTE To mute the speaker RESET To reset the system [password required] TAB To change time display mode ESC To the previous menu △...
  • Page 70 GST China Gulf Security Technology Co., Ltd. No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 Tel: +86 (0) 335 8502528 Fax: +86 (0) 335 8508942 Email: sales@gst.com.cn www.gst.com.cn GST UK Global System Technology PLC Lion Court, Staunton Harold Hall,...

Table of Contents