Installation Records (P300 To P346) - Siemens sitrans PROBE LU Instruction Manual

2-wire loop powered ultrasonic transmitter for level, volume and flow monitoring of liquids
Hide thumbs Also See for sitrans PROBE LU:
Table of Contents

Advertisement

P214 4 mA Output Trim
Note:
This parameter is for use only by Siemens Milltronics service personnel.
Calibrates the 4 mA output.
P215 20 mA Output Trim
Note:
This parameter is for use only by Siemens Milltronics service personnel.
Calibrates the 20 mA output.

Installation Records (P300 to P346)

P300 Temperature, transducer maximum
Shows the highest temperature encountered (in degrees C), as measured by the
temperature sensor in the transducer (if applicable).
Primary Index
Values (view only)
Press CLEAR
wiring.
P341 RUN Time
Displays the number of uninterrupted 24 hour periods that the device has been operating.
Values (view only)
Related
P341 is updated once a day.
If power is cycled before 24 hours have passed, the run time will not be updated.
If an instrument is powered down on a regular basis, P341 will not have an
accurate value.
7ML19985HT01
Transducer
Range
Default
then ENTER
, to reset the log after a short circuit on the transducer
Range
Default:
P342: Power-on Resets
SITRANS Probe LU – INSTRUCTION MANUAL
–50 to 150 oC (view only)
–50 (oC)
0 to 99999 (days)
0
Page 43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents