8 Diagnostics and servicing
Failure
Code
Text message
F013
No valid measured value
available
F017
Adjustment span too
small
F025
Error in the lineariza-
tion table
F036
no operable sensor soft-
ware
F040
Error in the electronics
F041
Communication error
F080
General software error
F105
Measured value is de-
termined
F113
Communication error
F260
Error in the calibration
F261
Error in the instrument
settings
52
7. Insert new O-ring seal for the process fitting
8. Install the process pressure transmitter in the welded socket,
tighten compression nut
The cleaning is finished.
The pressure transmitter is directly ready for operation, a fresh adjust-
ment is not required.
8.3

Diagnosis function

The following table shows the error codes and text messages of the
category "Failure" and provides information on causes as well as cor-
rective measures.
Reason
Gauge pressure or low pressure
Measuring cell defective
Adjustment not within specification
Index markers are not continuously ris-
ing, for example illogical value pairs
Failed or interrupted software update
Hardware defect
No connection to the sensor electronics
General software error
The instrument is still in the start phase,
the measured value could not yet be
determined
Error in the internal instrument com-
munication
Error in the calibration carried out in the
factory
Error in the EEPROM
Error during setup
Error when carrying out a reset
Rectification
Exchange measuring cell
Send instrument for repair
Change the adjustment according to the
limit values
Check linearisation table
Delete table/Create new
Repeat software update
Check electronics version
Exchanging the electronics
Send instrument for repair
Exchanging the electronics
Send instrument for repair
Check connection between sensor and
main electronics (with separate version)
Disconnect operating voltage briefly
Wait for the end of the switch-on phase
Disconnect operating voltage briefly
Send instrument for repair
Exchanging the electronics
Send instrument for repair
Repeat setup
Repeat reset
VEGABAR 82 • 4 ... 20 mA