Set Up Cybersentry And Change Default Password - GE L60 Instruction Manual

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CHAPTER 3: INSTALLATION
2.
Select the Ethernet interface and enter the IP address assigned to the L60, then click the Connect button. The
EnerVista UR Setup software creates a site named "Quick Connect" with a corresponding device also named "Quick
Connect" and displays them in the Online Window.
3.
Expand the sections to view data directly from the L60 device. Use the Device Setup button to change the site name.
Each time that the EnerVista software is initialized, click the Quick Connect button to establish direct communications to
the L60. This ensures that configuration of the EnerVista UR Setup software matches the L60 model number.

3.9 Set up CyberSentry and change default password

If and when first using CyberSentry security, use the following procedure for set up.
1.
Log in to the relay as Administrator by using the
(so that no IP address is required). If logging in through EnerVista choose Device authentication. Enter the default
password "ChangeMe1#". Note that the "Lock relay" setting needs to be disabled in the Security > Supervisory menu.
When this setting is disabled, configuration and firmware upgrade are possible. By default, this setting is disabled.
2.
Enable the Supervisor role if you have a need for it.
3.
Make any required changes in configuration, such as setting a valid IP address for communication over Ethernet.
4.
Log out of the Administrator account by choosing None.
Next, device or server authentication can be chosen on the login screen, but the choice is available only in EnerVista. Use
device authentication to log in using the five pre-configured roles (Administrator, Supervisor, Engineer, Operator, Observer,
or Administrator and Supervisor when device authentication is disabled). When using a serial connection, only Device
authentication is supported. When Server authentication is required, characteristics for communication with a RADIUS
server must be configured on the UR. This is possible only through the EnerVista software. The RADIUS server itself also
must be configured. At the end of this instruction manual, the appendix called RADIUS Server gives an example of how to
set up a simple RADIUS server. Once both the RADIUS server and the parameters for connecting UR to the server have
been configured, you can choose Server authentication on the login screen of EnerVista.
During the commissioning phase, you have the option to bypass the use of passwords. Do so by enabling the Bypass
Access setting under Settings > Product Setup > Security > Supervisory. Be sure to disable this bypass setting after
commissioning the device.
You can change the password for any role either from the front panel or through EnerVista.
If using EnerVista, navigate to Settings > Product Setup > Security. Change the Local Administrator Password, for
example. It is strongly recommended that the password for the Administrator be changed from the default. Changing the
passwords for the other three roles is optional.
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
SET UP CYBERSENTRY AND CHANGE DEFAULT PASSWORD
keys on the front panel or through EnerVista connected serially
VALUE
Figure 3-62: Login screen for CyberSentry
3
3-59

Advertisement

Table of Contents
loading

Table of Contents