8.

ELECTRIC CHARACTERISTICS

8-1.
OUTDOOR UNIT
Power Supply Full Load Characteristics
Voltage
Model name
Hz
(V)
AO G45LBT8
50
230
8-2.
BRANCH BOX
Power Supply
Voltage
Model name
Hz
(V)
UTP-PY03A
50
230
UTP-PY02A
50
230
Select the breaker based on MFA of the table above.
Select the wire size based on the larger value of MCA or MFA of the table above.
*1 Wiring Spec : These values are recommended data. Please select the wiring spec in accordance with local rules.
*2 Limited Wiring Length : This wiring length is in case voltage drop less than 2%. When wiring length extend longer,
select the wiring size of larger diameter.
MCA : Min Circuit Amp = Max Operating Current (Full Load)
MFA : Main Fuse (Circuit Breaker) Current
MSC : Max Starting Current
RLA : Rated Load Amp of compressor under the standard condition.
FLA : Full Load Amp of fan motor under the standard condition.
MCA
MFA
MSC
Power Cable
(A)
(A)
(A)
(mm
26.5
32
23.4
6
Full Load Characteristics
MCA
MFA
(A)
(A)
3
15
3
15
- (03 - 19) -
iring pecifications
Limited Wiring
Earth Cable
Length*2
2
2
)
(mm
)
(m)
6
16
iring pecifications
Power Cable
Earth Cable
2
(mm
)
(mm
2.5
2.5
2.5
2.5
3. OUTDOOR UNIT & BRANCH BOX
Compresser Outdoor Fan Motor
RLA
Output
(A)
(kW)
21
0.11
Limited Wiring
Length*2
2
)
(m)
14
14
FLA
(A)
0.9

Hide quick links: