3.5.2

Change the Bypass contactor

DISMANTLE THE SOFTSTARTER
Remove main power cables and control
cables
Disconnect the main power cables and the control
cables as described in chapter 3.3.3, step 1-3.
Remove cover and PCBA
Dismantle the front cover, all cables and the PCBA
as described in chapter 3.4.1, step 1-5.
1.
Remove PCBA bracket
1
Remove the PCBA bracket by lifting it upwards
from unit.
2.
Disconnect flexible bars
1
Loosen (3x)
Torx 30 M6x25 (one screw per
phase) to disconnect the flexible bars.
3.
Remove bypass contactor
1
Loosen (4x)
Torx 25 M3x8 from the bypass
contactor.
2
Loosen (3x)
Torx 30 M6x25 from the
bypass contactor.
3
Remove the bypass contactor (including cable)
by lifting it upwards from unit. Dispose of expended
bypass contactor.
1
2
3
1
3
| Service Manual | Service PSTX210...370
1SFC13105M0201
1
3.5.2_1
1
Tx 30
M6 x 25
3.5.2_2
2
Tx 25
Tx 30
M5 x 18
M6 x 25
3.5.2_3
3
31