Configuration; Configuration With Pushbutton Display - GE Masoneilan SVI II ESD Installation And Maintenance Manual

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

Configuration

To perform configuration and calibration you can use either pushbutton display, HART
handheld communicator, HART
"Pushbuttons and Local Display" on page 98 or the SVI II ESD Help for instructions.
The following section describes configuration and calibration procedure using optional local
display and pushbuttons.

Configuration with Pushbutton Display

To change the current configuration parameters:
1. After power up, if SVI II ESD is not in NORMAL mode, switch to NORMAL mode. The display
alternates between POS and SIGNAL indicating NORMAL mode.
2. Press + to until MANUAL appears.
3. Press * to select MANUAL mode. The display alternates between POS –M and SIG
indicating MANUAL mode.
4. Press * and SETUP appears.
5. Press * again and
6. Press * to access CONFIGuration menu.
7. Set the configuration parameters: Air Action, Air Pressure Units and Language by:
a. Pressing * to access and change the parameter.
b. Pressing + to move to the next parameter.
8. Press + to return to SETUP.
9. Press + to return to NORMAL mode.
88 |
=GE Oil & Gas
®
Host with the DD loaded, or ValVue ESD software. Refer to
These procedures can cause the valve to move. Before proceeding
WARNING
be sure that the valve is isolated from the process. Keep hands
clear from moving parts.
CONFIG appears.