Application Set-Up Examples
6 Application Set-Up Examples
6.1 Introduction
The examples in this section are intended as a quick
reference for common applications.
•
Parameter settings are the regional default values
unless otherwise indicated (selected in
K-03 Regional Settings)
•
Parameters associated with the terminals and
their settings are shown next to the drawings
•
Where switch settings for analog terminals A53 or
A54 are required, these are also shown
6
6
6.2 Application Examples
Table 6.1 Analog Speed Reference (Voltage)
40
AF-650 GP Operating Instructions
Parameters
Function
Setting
AN-10 Terminal
53 Low Voltage
0.07V*
AN-11 Terminal
10V*
53 High Voltage
AN-14 Terminal
0RPM
53 Low Ref./
Feedb. Value
AN-15 Terminal
1500RPM
53 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
AN-12 Terminal
53 Low Current
AN-13 Terminal
53 High Current
AN-14 Terminal
53 Low Ref./
Feedb. Value
AN-15 Terminal
53 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
Table 6.2 Analog Speed Reference (Current)
E-01 Terminal 18
Digital Input
E-07 Terminal 37
Safe Stop
* = Default Value
Notes/comments:
Table 6.3 Start/Stop Command with Safe Stop
Parameters
Function
Setting
4mA*
20mA*
0RPM
1500RPM
Parameters
Function
Setting
[8] Start*
[1] Safe Stop
Alarm