Advertisement

5.8 INPUTS AND OUTPUTS
GOOSE Analogs can be compared to other GOOSE Analogs with any character string or no string.
GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-
log values in other C70 features, such as FlexElements. The base factor is applied to the GOOSE analog input Flex-
Analog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
The per-unit base setting represents thousands, not single units. For example, a PU base of 1.000 is actually 1000 and
a PU base of 0.001 is 1.
When using GOOSE Analogs and PU base in FlexElements, the largest value that can be displayed in the FlexEle-
ment actual values is 2,140,000.000.
Table 5–34: GOOSE ANALOG INPUT BASE UNITS
ELEMENT
dcmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE POWER
SOURCE THD & HARMONICS
SOURCE VOLTAGE
5
The GOOSE analog input FlexAnalog values are available for use in other C70 functions that use FlexAnalog values.

PATH: SETTINGS
INPUTS/OUTPUTS
 GOOSE UINTEGER
 INPUT 1
The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger values between any two UR-series
devices. The following settings are available for each GOOSE uinteger input.
UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the
UINTEGER 1 DEFAULT MODE
number.
UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is "Last Known", the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
"Default Value", then the value of the GOOSE uinteger input is defined by the
The GOOSE integer input FlexInteger values are available for use in other C70 functions that use FlexInteger values.
5-260
BASE UNITS
BASE = maximum value of the
under the +IN and –IN inputs.
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
BASE = 1%
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE

IEC 61850 GOOSE UINTEGERS
UINTEGER
1000
UINTEGER
MESSAGE
MODE: Default Value
is set to "Default Value".This setting is stored as a 32-bit unsigned integer
C70 Capacitor Bank Protection and Control System
setting for the two transducers configured
DCMA INPUT MAX
× I
for the +IN and –IN inputs
BASE
BASE

5.8.12 IEC 61850 GOOSE INTEGERS


GOOSE UINTEGER INPUT 1(16)
Range: 0 to 429496295 in steps of 1
1 DEFAULT:
Range: Default Value, Last Known
1 DEFAULT
UINTEGER 1 DEFAULT
5 SETTINGS
setting.