Table A.1 Firmware Revision History (Sheet 3 of 5)
Firmware Identification (FID) Number
This firmware differs from the previous version as follows:
SEL-351S-x-R113-V0-Z005005-D20030908
This firmware differs from the previous version as follows:
SEL-351S-x-R112-V0-Z005005-D20030714
This firmware differs from the previous version as follows:
SEL-351S-x-R111-V0-Z005005-D20030212
This firmware differs from the previous version as follows:
SEL-351S-x-R110-V0-Z005005-D20021106
This firmware applies to the manual date code listed:
SEL-351S-x-R110-V0-Z005005-D20020725
This firmware differs from the previous version as follows:
SEL-351S-x-R109-V0-Z005005-D20020725
This firmware differs from the previous version as follows:
SEL-351S-x-R108-V0-Z005005-D20020711
Date Code 20080103
Description of Changes
CT saturation protection was enhanced to improve security with
low-set instantaneous values.
Corrected rounding error in breaker wear monitor.
Optimized calibration settings for Petersen Coil units to
improve the factory calibration process.
Corrected improper metering and protection on 0.05 A neutral
CT for secondary currents in the range of 0.045–0.120A. This
affects firmware versions R108–R110 with part numbers
0351Sxxxxxx(8 or 9)xxx.
Added CT Saturation Protection.
Limited TCLOSD setting step size to 0.25 cycle increments.
Added Rollover feature for all Energy Values (MWhA
MWhA
, MWhB
, etc.). All Energy Values will rollover at
OUT
IN
100000.
Manual update only. See
Table A.2
updates.
Updated the calibration settings for manufacturing. (This is the
first shipping released that includes all of the changes listed
under R108 below, which was never shipped.)
Added global setting PTCONN to allow the relay VA, VB, VC, and
N input terminals to be connected to wye-connected PTs (as
before), or open-delta connected PTs.
Added global setting VSCONN to allow the relay VS-NS termi-
nals to be connected to a synchronism check voltage source (as
before), or a broken-delta zero-sequence voltage source.
Added ground directional element options for low-impedance,
Petersen coil, and ungrounded/high-impedance grounded sys-
tems (expanded setting options for setting ORDER [S, P, and
U]). These new directional element options require the new
option of a 0.2 A nominal neutral channel (IN) current input.
Supervising LOP (loss-of-potential) logic is removed from
directional element logic (with outputs F32x and R32x) and put
into preceding internal enable logic (with outputs 32xE).
Extended the lower end of the pickup setting range of the resid-
ual ground instantaneous/definite-time overcurrent elements
50G1–50G6/67G1T–67G6T (from 0.05 A to 0.01 A for 1 A
nominal phase current inputs; from 0.25 A to 0.05 A for 5 A
nominal phase current inputs). Also, an intentional 2-cycle
built-in delay is added to the residual ground instantaneous/ def-
inite-time overcurrent elements—this delay is active for the new
extended lower range only.
Extended the lower end of the pickup setting range of the resid-
ual ground time-overcurrent elements 51G1T and 51G2T (from
0.1 A to 0.02 A for 1 A nominal phase current inputs; from
0.5 A to 0.1 A for 5 A nominal phase current inputs).
Instruction Manual
Firmware and Manual Versions
Manual Date
,
IN
for a summary of manual
A.3
Firmware
Code
20030908
20030714
20030212
20021106
20021009
20020725
20020711