Addressing Sd Slc Devices; Sd505-Photo Or Sd505-Heat - SILENT KNIGHT Intelliknight 5700 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Model 5700 Installation Manual
5.8

Addressing SD SLC Devices

This section tells how to address detectors and modules.
5.8.1

SD505-PHOTO or SD505-HEAT

The SD505-PHOTO photoelectric smoke detector and SD505-HEAT heat detector are easily addressed at the
FACP. The Installer Code is required to perform this task.
To address a SD505-PHOTO or SD505-HEAT:
1.
Connect a detector base temporarily to the programming terminals as shown in
Figure 5-7. (You can use the same base for each detector.)
Figure 5-7 Temporary Connection of Detector Base to Panel for Addressing
2.
Enter the Installer code, then press
3.
Select 2 for Point Functions.
4.
Select 3 for Set SLC Dev Addr.
5.
Select "Yes" by pressing the
You can use the SILENCE key to stop the PZT. The trouble will clear automatically when the panel reinitial-
izes when you finish programming.)
6.
When the wait message clears, the following options display:
1- for Read Address. Use to read (or check) a single detector's address.
2- for Write Address. Use to program a single detector's address.
3- for Seq. Programming. Use to program more than one detector in sequential order.
7.
If you are changing addresses, write the programmed address on the back of the device.
8.
To exit press left arrow until fully exited.
.
ENTER
up arrow, then press
ENTER
5-9
. (The panel will go into trouble at this point.