Toshiba TOSVERT VF-AS1 Function Manual page 14

Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

(2) Input signal
Inverter -> Master unit
The following shows input signals to the master unit. (The output signals for the inverter.)
Device No.
Signal name
RXn0
Forward running
RXn1
Reverse running
RXn2
Output terminal selection 1 (OUT1) The function depends on output terminal function selection 1 ( f130 ).
RXn3
Output terminal selection 2 (OUT2) The function depends on output terminal function selection 2 ( f131 ).
RXn4
Output terminal selection 3 (FL) The function depends on output terminal function selection 3 ( f132 ).
RXn5
Output terminal selection 4 (OUT3) The function depends on output terminal function selection 4 ( f133 ).
RXn6
Output terminal selection 5 (OUT4) The function depends on output terminal function selection 5 ( f134 ).
RXn7
Output terminal selection 6 (R1) The function depends on output terminal function selection 6 ( f135 ).
RXn8
Output terminal selection 7 (OUT5) The function depends on output terminal function selection 7 ( f136 ).
RXn9
Output terminal selection 8 (OUT6) The function depends on output terminal function selection 8 ( f137 ).
RXnA
Output terminal selection 9 (R2) The function depends on output terminal function selection 9 ( f138 ).
RXnB
Reserved
RXnC
Monitoring
Frequency setting completion
RXnD
(RAM)
Torque setting completion
RXnE
(RAM)
Instruction code execution
RXnF
completion
RX(n+1)0
:
Reserved
RX(n+1)7
RX(n+1)8 Reserved
RX(n+1)9 Reserved
RX(n+1)A Error status flag
RX(n+1)B Remote station ready
RX(n+1)C
:
Reserved
RX(n+1)F
"n" is depend on the station number.
OFF: Other than forward running (during stop or reverse rotation)
ON : Forward running
OFF: Other than reverse running (during stop pr forward rotation)
ON : Reverse running
Reserved for the system.
Switched on when the monitored value is set to RWrn by the
monitor command (RYnC) switching on. Switched off when the
monitor command (RYnC) is switched off.
Switched on when the set frequency is written to the inverter by the
frequency setting command (RYnD) switching on. Switched off
when the frequency setting command (RYnD) is switched off.
Switched on when the set torque is written to the inverter by the
torque setting command (RYnE) switching on. Switched off when
the torque setting command (RYnE) is switched off.
Switched on on completion of the processing corresponding to the
instruction code (RWw+2) which is executed when the instruction
code execution request (RYnF) switches on. Switched off when the
instruction code execution completion (RXnF) is switched off.
Reserved for the system.
Reserved for the system.
Reserved for the system.
Switched on when occurred an inverter error or option error
(watchdog error, CPU error, ROM error, RAM error). It is not
switched on besides that.
Switched on when the inverter goes into the ready status on
completion of initial setting after power-on or hardware reset.
(Used as an interlock for read/write from/to the master unit.)
Switched off when an inverter error occurs (protective function is
activated).
Reserved
12  −
− 
Description