Operation
6.5 Local operation
Condition for "setting"
You are familiar with the correct operation of the transmitter and the associated safety notes.
Setting electrical damping
To set electrical damping to 0 seconds, proceed as follows:
1. Set mode 4.
2. Press the [↑] and [↓] buttons simultaneously.
3. Save with the [M] button.
Result
Electrical damping has been set to 0 seconds.
Condition for "adjusting"
The default setting of steps is an interval of 0.1 seconds. If you press the [↑] or [↓] button for
a longer time, the step is increased.
Adjusting electrical damping
To adjust electrical damping, proceed as follows:
1. Set mode 4.
2. Adjust the desired damping.
3. Save with the [M] button.
Result
Electrical damping has been set to the desired time constant.
See also
Operation using buttons (Page 79)
Electrical damping (filter time constant) (Page 116)
6.5.4

Calibrate zero point

Introduction
You can calibrate the zero point in mode 7. A zero point calibration is used to correct zero
errors resulting from the mounting position of the transmitter. You must proceed differently
depending on the device version.
80
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07