APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 51 of 71)
ADDR
REGISTER NAME
Pilot POTT1 (1P) (Read/Write Setting)
A830
POTT1 1P Scheme Function
A831
POTT1 1P Permissive Echo
A832
POTT1 1P Rx Pickup Delay
A833
POTT1 1P Trans Block Pickup Delay
A834
POTT1 1P Trans Block Reset Delay
A835
POTT1 1P Echo Duration
A836
POTT1 1P Echo Lockout
A837
POTT1 1P Line End Open Pickup Delay
A838
POTT1 1P Seal In Delay
A839
POTT1 1P Ground Directional Overcurrent Forward
A83B
POTT1 1P Number of Communication Bits
A83C
POTT1 1P Rx1
A83E
POTT1 1P Rx2
A840
POTT1 1P Rx3
A842
POTT1 1P Rx4
A844
POTT1 1P Target
A845
POTT1 1P Event
A846
POTT1 1P Echo Condition
A848
POTT1 1P Scheme Block
A84A
POTT1 1P OC Fwd2
A84C
POTT1 1P OC Fwd2
A84E
Reserved (22 items)
Frequency Rate of Change (Read/Write Setting) (4 modules)
A900
Frequency Rate of Change 1 Function
A901
Frequency Rate of Change 1 OC Supervision
A902
Frequency Rate of Change 1 Min
A903
Frequency Rate of Change 1 Max
A904
Frequency Rate of Change 1 Pickup Delay
A905
Frequency Rate of Change 1 Reset Delay
A906
Frequency Rate of Change 1 Block
A908
Frequency Rate of Change 1 Target
A909
Frequency Rate of Change 1 Events
A90A
Frequency Rate of Change 1 Source
A90B
Frequency Rate of Change 1 Trend
A90C
Frequency Rate of Change 1 Pickup
A90D
Frequency Rate of Change 1 OV Supervision
A90E
Frequency Rate of Change 1 Reserved (3 items)
A911
...Repeated for Frequency Rate of Change 2
A922
...Repeated for Frequency Rate of Change 3
A933
...Repeated for Frequency Rate of Change 4
IEC 61850 received analog settings (read/write) (32 modules)
AA00
IEC 61850 GOOSE analog 1 default value
AA02
IEC 61850 GOOSE analog input 1 mode
AA03
IEC 61850 GOOSE analog input 1 units
AA05
IEC 61850 GOOSE analog input 1 per-unit base
AA07
...Repeated for IEC 61850 GOOSE analog input 2
AA0E
...Repeated for IEC 61850 GOOSE analog input 3
AA15
...Repeated for IEC 61850 GOOSE analog input 4
AA1C
...Repeated for IEC 61850 GOOSE analog input 5
AA23
...Repeated for IEC 61850 GOOSE analog input 6
AA2A
...Repeated for IEC 61850 GOOSE analog input 7
AA31
...Repeated for IEC 61850 GOOSE analog input 8
AA38
...Repeated for IEC 61850 GOOSE analog input 9
GE Multilin
RANGE
0 to 1
0 to 2
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 4294967295
0 to 2
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 30
20 to 80
20 to 80
0 to 65.535
0 to 65.535
0 to 4294967295
0 to 2
0 to 1
0 to 5
0 to 2
0.1 to 15
0.1 to 3
0 to 1
–1000000 to 1000000
0 to 1
---
0 to 999999999.999
L90 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F199
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F198
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F001
---
1
F102
pu
0.001
F001
Hz
0.01
F001
Hz
0.01
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F167
---
1
F224
Hz/s
0.01
F001
pu
0.001
F001
---
1
F001
---
0.001
F060
---
1
F491
0 (Default Value)
---
---
F207
---
0.001
F060
DEFAULT
0 (Disabled)
0 (Disabled)
0
20
B
90
100
250
50
0
0
0 (1)
0
0
0
0
0 (Self-reset)
0 (Disabled)
0
0
0
0
0
0 (Disabled)
200
4500
6500
0
0
0
0 (Self-reset)
0 (Disabled)
0 (SRC 1)
0 (Increasing)
50
700
0
1000
(none)
1
B-59