GE L90 Instruction Manual page 260

Ur series line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

5.5 FLEXLOGIC
Table 5–10: L90 FLEXLOGIC OPERANDS (Sheet 9 of 10)
OPERAND TYPE
OPERAND SYNTAX
FIXED OPERANDS
Off
On
INPUTS/OUTPUTS:
Cont Ip 1
Contact inputs
Cont Ip 2
Cont Ip 1
Cont Ip 2
INPUTS/OUTPUTS:
Cont Op 1
Contact outputs,
Cont Op 2
current
(from detector on
form-A output only)
INPUTS/OUTPUTS:
Cont Op 1
Contact outputs,
Cont Op 2
voltage
(from detector on
Cont Op 1
form-A output only)
Cont Op 2
INPUTS/OUTPUTS:
Direct I/P 1-1 On
Direct input
Direct I/P 1-8 On
Direct I/P 2-1 On
Direct I/P 2-8 On
5
INPUTS/OUTPUTS:
RemDPS Ip 1 BAD
Remote double-
RemDPS Ip 1 INTERM
point status inputs
RemDPS Ip 1 OFF
RemDPS Ip 1 ON
REMDPS Ip 2...
INPUTS/OUTPUTS:
REMOTE INPUT 1 On
Remote inputs
REMOTE INPUT 2 On
REMOTE INPUT 2 On
REMOTE INPUT 32 On
INPUTS/OUTPUTS:
Virt Ip 1
Virtual inputs
Virt Ip 2
Virt Ip 3
Virt Ip 64
INPUTS/OUTPUTS:
Virt Op 1
Virtual outputs
Virt Op 2
Virt Op 3
Virt Op 96
LED INDICATORS:
LED IN SERVICE
Fixed front panel
LED TROUBLE
LEDs
LED TEST MODE
LED TRIP
LED ALARM
LED PICKUP
LED VOLTAGE
LED CURRENT
LED FREQUENCY
LED OTHER
LED PHASE A
LED PHASE B
LED PHASE C
LED NEUTRAL/GROUND
LED INDICATORS:
LED TEST IN PROGRESS
LED test
LED INDICATORS:
LED USER 1
User-programmable
LED USER 2 to 48
LEDs
5-130
OPERAND DESCRIPTION
Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as 'Disable' by other features.
Logic = 1. Can be used as a test setting.
On
(will not appear unless ordered)
On
(will not appear unless ordered)
Off
(will not appear unless ordered)
Off
(will not appear unless ordered)
IOn
(will not appear unless ordered)
IOn
(will not appear unless ordered)
VOn
(will not appear unless ordered)
VOn
(will not appear unless ordered)
VOff
(will not appear unless ordered)
VOff
(will not appear unless ordered)
(appears only when an inter-relay communications card is used)
(appears only when inter-relay communications card is used)
(appears only when inter-relay communications card is used)
(appears only when inter-relay communications card is used)
Asserted while the remote double-point status input is in the bad state.
Asserted while the remote double-point status input is in the intermediate
state.
Asserted while the remote double-point status input is off.
Asserted while the remote double-point status input is on.
Same set of operands as per REMDPS 1 above
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
Asserted when the front panel IN SERVICE LED is on.
Asserted when the front panel TROUBLE LED is on.
Asserted when the front panel TEST MODE LED is on.
Asserted when the front panel TRIP LED is on.
Asserted when the front panel ALARM LED is on.
Asserted when the front panel PICKUP LED is on.
Asserted when the front panel VOLTAGE LED is on.
Asserted when the front panel CURRENT LED is on.
Asserted when the front panel FREQUENCY LED is on.
Asserted when the front panel OTHER LED is on.
Asserted when the front panel PHASE A LED is on.
Asserted when the front panel PHASE B LED is on.
Asserted when the front panel PHASE C LED is on.
Asserted when the front panel NEUTRAL/GROUND LED is on.
An LED test has been initiated and has not finished.
Asserted when user-programmable LED 1 is on.
The operand above is available for user-programmable LEDs 2 through 48.
L90 Line Current Differential System
5 SETTINGS