Command source, setpoint source, and application parameters
With the next step, you can select whether the Basic Operator Panel or the terminal should be
the command source (parameter P700). In the case of the CU240E-2 being used here, the termi-
nals are set as the default for the command source.
Selecting command source (P700)
• Press OK to modify the parameter value CMD SRC.
• Check to see if it shows TERMINAL and the value 2.
• Confirm by pressing OK.
The next step is checking the setpoint source. This is stored with P1000.
Checking the setpoint source (P1000)
• Press OK to modify the parameter value MAIN SP.
• Check if it shows ANALOG and the value 2.
• The 2 indicates that the potentiometer on the terminal is currently set as the
• Confirm by pressing OK.
Now you should adjust the operating behavior of the motor to your application.
Additional setpoint source (P1000)
• Press OK to modify the parameter value ADD SP.
• This parameter gives you the possibility to add a second setpoint source by pressing
• Leave the value at NONE (0) and confirm by pressing OK.
Operator Panels BOP-2 and IOP:
28
OK
setpoint source.
OK
UP or DOWN.
OK
Quick commisioning
OK
OK
OK