RT430/434
Amplitude Modulated Output
Serial Port (RS232, RS422/485)
32
See the Technical Specification chapter for optical outputs technical information.
The RT430/434 has one amplitude-modulated output, which generates an IRIG-B124
signal. Use coaxial cables with an impedance of 50 Ω and a BNC connector on this
output. See the Technical Specification chapter for the signal levels description.
Figure 18: Amplitude modulated output
The serial port is compatible with the RS232 and RS422/485 standard (DTE pin-
layout). The RS422/485 is capable of synchronizing up to 32 devices.
Figure 19: Serial port RS232 and RS422/485
Table 1: Serial port pinout
DB9 male
Signal
1
-
2
TXD (used to send the datagram)
3
RXD
Figure 17: Optical outputs
Chapter 4 – Installation
RT430/434