Climatic Stress Tests - Siemens SIPROTEC 7SD610 Manual

Hide thumbs Also See for SIPROTEC 7SD610:
Table of Contents

Advertisement

Technical Data
4.1 General
Vibration and Shock Resistance during Transport
Standards:
Oscillation
IEC 60255-21-1, Class 2
IEC 60068-2-6
Shock
IEC 60255-21-2, Class 1
IEC 60068-2-27
Continuous shock
IEC 60255-21-2, Class 1
IEC 60068-2-29
4.1.7

Climatic stress tests

Climatic tests
Standards:
Type tested (acc. to IEC 60068-2-1 and -2,
Test Bd for 16 h)
Permissible temporary operating temperature (tested for
96 h)
Recommended for permanent operation (according to
IEC 60255-6)
Limit Temperatures for Storage
Limit Temperatures during Transport
Storage and transport of the device with factory packaging!
1)
Limit temperature for normal operation
(i.e. output relays not energized)
1)
Limit temperature with maximum load
(max. cont. permissible input and output quantities)
1)
UL–certified according to standard 508 (Industrial Control Equipment)
Humidity
Admissible humidity
It is recommended that all devices be installed so that they are not exposed to direct sunlight nor subject to large fluctua-
tions in temperature that may cause condensation to occur.
332
IEC 60255-21 and IEC 60068
Sinusoidal
5 Hz to 8 Hz: ± 7.5 mm Amplitude;
8 Hz to 150 Hz: 2 g acceleration
frequency sweep 1 octave/min
20 cycles in 3 orthogonal axes
Semi-sinusoidal
15 g acceleration, duration 11 ms,
each 3 shocks (in both directions of the 3 axes)
Semi-sinusoidal
10 g acceleration, duration 16 ms,
1000 shocks each in both directions of the 3 axes
IEC 60255-6
-25 °C to +85 °C or -13 °F to +185 °F
-20 °C to +70 °C or -4 °F to +158 °F
(legibility of display may be restricted from +131 °F (+55 °C))
-5 °C to +55 °C or 23 °F to +131 °F
when max. half of the inputs and outputs are subjected to the
max. permissible values
-25 °C to +55 °C or -13 °F to +131 °F
-25 °C to +70 °C or -13 °F to +158 °F
-20 °C to +70 °C or -4 °F to +158 °F
-5 °C to +55 °C or -23 °F to +131
Annual average ≤ 75 % relative humidity;
On 56 days of the year up to 93% relative humidity. Condensa-
tion must be avoided in operation!
C53000-G1176-C145-6, Release date 02.2011
SIPROTEC, 7SD610, Manual