5.3 Electrical Connections –
Fig. 5.5 (overleaf)
Warning. Before making
any connections, ensure that the
power supply, any powered control
circuits and high common mode
voltages are switched off.
Note. If it is not possible to
avoid strong electrical and magnetic
fields,
screened
earthed metal conduit must be used.
5.4 Relays, Arc Suppression,
Inputs and Outputs

5.4.1 Relay Contact Ratings

Relay contacts are rated at:
115/230V AC at 5A (non-inductive)
250V DC 25W max.

5.4.2 Arc Suppression

Arc suppression components are fitted
to relays 2 and 3 only. If relay 1 is
required to switch inductive loads, fit
the
arc
suppression
supplied.
cables
within
components
5 INSTALLATION...

5.4.3 Logic Output

18V DC at 20mA
Min load 900Ω
Isolated
from
(not isolated from Retransmission
O/P).
Dielectric strength: 500V d.c. for 1
minute.
5.4.4 Retransmission
Analog Output
Max. load 15V (750Ω at 20mA)
Isolated from Analog Input (not
isolated from Logic O/P).
Dielectric strength: 500V d.c. for 1
minute.

5.4.5 Digital Input

Type: Volt-free
Minimum Pulse: 250 ms