V V V V I I I I S S S S T T T T A A A A - - - - 3 3 3 3 2 2 2 2 F F F F B B B B V V V V I I I I S S S S...
Page 2
Recommended Programming Procedure....6 System Layout Worksheets........40 Program Field Index ..........7 Output Devices Worksheets ........47 VISTA-32FB Programming Form ......8 Scheduling Menu Prompts ........53 Partition-Specific Fields.......... 14 Scheduling Worksheets.......... 54 Programming With #93 Menu Mode ...... 16 5800 Series Transmitters Loop Designations ..
Page 3
Program feature or option Permitted in Possible settings Settings permitted in UL 864 UL864? Y/N ✱ 80 ZONE TYPE RESTORES 0 = disable Must be set to “1” (enable) for zone FOR TYPES 9, 10 & 14 1 = enable type 9.
Page 4
Program feature or option Permitted in Possible settings Settings permitted in UL 864 UL864? Y/N 0 = disable Must be set to “0” (disable) for 2✱ 24 DISPLAY TROUBLES OF 1 = enable partition 1. OTHER PARTITIONS 0 = disable Must be set to “1”...
Page 5
Following the program forms are system layout worksheets. We recommend that you use these sheets to plan your system before programming is performed. If you need further information about specific programming options, see the VISTA-32FB Installation and Setup Guide .
11. Define user access codes. Refer to User Access Codes in the VISTA-32FB Installation and Setup Guide to program authority level, O/C reporting option, partition assignments, and wireless key assignments for each user. 12. Exit Programming Mode.
Page 7
Program Field Index On the following pages, the programming fields have been arranged in numerical order. Use this index to cross-reference the fields on the programming form. Field Group Field Group Field Group System-Wide Communications 1*58 System-Wide System-Wide Communications 1*60 System-Wide Partition-Specific Communications...
Page 8
VISTA-32FB Programming Form Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system, see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ];...
Page 9
DOWNLOAD PHONE NO. DUAL REPORTING 1=yes; 0=no If used with Spilt Reporting "1" option (1*34), alarms and alarm restores go to both primary and secondary numbers, while all other reports go to secondary only. If used with Split Reporting "2" option, alarms and alarm restores go Enter 0-9 for each digit.
Page 10
1*21 FOR TYPES 9, 10 and 14 EXIT DELAY RESET 0=No; 1=Resets Exit Delay to programmed value after zone 1=enable; [0=disable] is closed and then faulted prior to end of exit delay. Restores must be set to “1” for Commercial Fire installations. Must be "0"...
Page 11
1*44 1*72 WIRELESS KEYPAD TAMPER DETECTION EVENT LOG PRINTER ON-LINE - – Not Not Used. Must Be Used. Must be set to “0”. Set To “0”. 1=enable; 0=disable. 0=disable; 1=enable 1*45 EXIT DELAY SOUNDING 1*73 PRINTER BAUD RATE - Not Used. Must Be Set To “0”..
Page 12
2*09 3*12 OPEN/CLOSE REPORTS BY EXCEPTION [0] ZN TYPE 18 DELAY USE 1=enable; 0=disable 0=disable; 1=enable NOTE: Must be set to “0” for Commercial Fire Installations. If enabled, only openings and closings occurring outside the scheduled opening/closing windows will trigger dialer reports. Opening reports will also be suppressed during the closing 3*13 FIRE SUPERVISORY RESPONSE TO OPEN/SHORT...
Page 13
3*57 3*61 BELL 2 & AUX RELAY CONFIRM [0,0] AUX RELAY FUNCTION 0=trouble/supervisory; 1=alarm, silenced by code = off; ARMING DING Bell 2 2=smoke detector reset; 3=battery save; 4=alarm, silenced 0=disable; 1=enable. by code = # = 67 NOTE: If using a keyfob, when the button is pressed, either NOTE: See Data Field Descriptions in the Installation and for arming or disarming, the bell will ding indicating that the Setup Guide for specific information.
Page 14
Partition-Specific Fields (Duplicate this page for each partition in the installation.) To program these fields, 1. Press *91 to select a partition. 2. Enter a partition-specific field number (ex. *09). 3. Make the required entry. 4. Repeat steps 1-3 for each partition in the system. PARTITION #____ PROGRAM FIELDS 1st Page Fields ENABLE OPEN/CLOSE REPORT...
Page 15
1*45 2*18 EXIT DELAY SOUNDING ENABLE GOTO FOR THIS PARTITION 1=enable; 0=disable Produces quick beeping during exit 1=Allow log-on from other partitions; 0=disable NOTE: Must be disabled (0) for partition 1 in Commercial delay if enabled. NOTES: Fire installations. Must be set to “0” in partition 1 for fire systems. 2*20 ENABLE J2 TRIGGERS BY PARTITION See page 31, “SOUND OPTION”, prompt for disabling the...
Page 16
Programming With #93 Menu Mode NOTE: The following field should be preset before beginning: 2*00 Number of Partitions. In addition, receivers should be programmed via Device programming. After programming all system related programming fields in the usual way, press #93 while still in programming mode to display the first choice of the menu driven programming functions.
PROMPT EXPLANATION Not Used. Must be set to “0”. CUSTOM INDEX? 1 = YES 0 = NO Not Used. Must be set to “0”. ACCESS POINT PGM 1 = YES 0 = NO Not Used. Must be set to “0”. ACCESS GRP PGM 1 = YES 0 = NO...
Page 18
Each zone must be assigned a zone type, which defines the way in which the system responds to faults in 010 ZONE TYPE that zone. Refer to the Zone Type Definitions section in the VISTA-32FB Installation and Setup Guide for PERIMETER detailed definitions of each zone type.
Page 19
PROMPT EXPLANATION If input type 3 or 6 was selected, this prompt will be displayed. Enter 1 for devices that monitor maintenance 010 SMART CONTACT signals (ex. 5193SD, 5193SDT) or can be used to limit fault signals in the disarmed state (ex. Quest 1 = YES 0 = NO 2260SN).
5800 Series Transmitters Loop Designations PROMPT EXPLANATION Confirmation Option: This prompt only appears if you answered “Yes” at the first prompt. The system XMIT TO CONFIRM enters a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate PRESS ✱TO SKIP the loop input or button that corresponds to this zone.
Expert Mode Zone Programming Expert mode allows you to program zones using the minimum number of screens and keystrokes. Enter the Programming mode with [Installer Code] + 8 0 0 Before programming your zones, do the following: Program field 2✱00: Number of Partitions. Enable your RF Receiver in Device Programming menu mode.
Page 22
PROMPT EXPLANATION If you entered RM, RF, BR, UR or SL for the Input Type, this screen displays. Otherwise the summary 010 INPUT S/N: screen for the next zone displays. A XXX-XXXX Enter the 7-digit serial number, using one of the following methods: a.
All report codes are entered using #93 Menu Mode Programming , either through Report Code Programming , or through Zone Programming while entering other zone information. In the VISTA-32FB, reports are divided into six categories. These categories represent the main menu options in Report Code Programming . Reports and the categories in which they are...
Page 24
Restore/Supervisory Codes PROMPT EXPLANATION Press [1] (Y) to enter Restore and Supervisory Codes for zones. RESTR, SUPV. CODE 1 = YES 0 = NO Enter one zone for each group of 16 zones (001-016, 017-032, etc.). ENTER ZN FOR GRP 000 = QUIT Enter the first digit of the Alarm Restore Report Code for this group of zones (double-digit entry).
Page 25
PROMPT EXPLANATION Enter the rest of the codes in the same manner. Other report codes in System Group #1 are: • Opening (Disarm) Also, enable this if you desire Callback Requested reports (the panel answers a phone call from the downloader). •...
Page 26
PROMPT EXPLANATION Enter the rest of the codes in the same manner. Other codes in System Group #3 are: • Early Close • Late Open • Late Close • Failed to Open • Failed to Close • Auto-Arm Failed • Schedule Change Once you have entered these report codes, the system prompts you with the Quit menu.
Alpha Descriptors Programming You can program a user-friendly English language description/location for all protection zones, relays, keypad panics, polling loop short, and RF receiver supervision troubles. Each description can be composed of a combination of words (up to 3) that are selected from a vocabulary of 244 words stored in memory, and any word can have an "s"...
Page 28
Accept the word. To accept the word, press [6], which switches back to the alphabet list for the next word, or press [8] to store the complete descriptor and then exit. Select the next word. For selection of the next word (DOOR), repeat step 3a (word #063) or 3b, but selecting the word "DOOR.” To accept the word, press [6], which again switches back to alphabet list.
Page 29
Type the word using one of two methods as follows: Press [#], followed by the 2-digit entry for the first letter you would like to display (e.g., 65 for "A"). When the desired character appears, press [6] to select it. The cursor will then move to the right, in position for the next character.
Alpha Descriptor Vocabulary (For entering alpha descriptors. To select a word, press [#] followed by the word's 3-digit number.) NOTE: This vocabulary is not to be used for relay voice descriptors. See the Relay Voice Descriptors section when programming relay voice descriptors. 000 (Word Space) •...
Device Programming This menu is used to program keypads, receivers, and relay modules, etc. Device Address 00 is always set as an alpha keypad assigned to Partition 1 with no sounder suppression options, and these settings cannot be changed. From Data Field Programming mode, press #93 to display "ZONE PROG?" Press [0] repeatedly to display "DEVICE PROG?" PROMPT EXPLANATION Press [1] to enter Device Programming .
Page 32
Output Relay Module PROMPT EXPLANATION If you selected device type 04 (relay module), this prompt appears. Enter 1 if the unit is a 4204CF. If not, 01 SUPERVISED CF? enter 0. If you enter 1, only Relay 1 (Output A) and Relay 3 (Output B) on each module may be programmed for functions.
Page 33
The 6160/6160CR-2 Keypad displays the following prompts, which are sent by the Communicator to the control. NOTE: These prompts are for the 7845i-ent Communicator only. If you are using a different communicator, refer to the communicator’s instructions for the correct prompts. PROMPT EXPLANATION Enter the device address of the Communicator.
Output Programming The system supports up to 96 outputs. Outputs can be used to perform many different functions and actions. Each output must be programmed to begin one of four types of ACTIONS at a designated START event, and end that ACTION at a designated STOP event.
Page 35
STOP (STP): The "STOP" programming determines when and under what conditions the device is de-activated. The following options are available: 1). RESTORE ZONE LIST (ZL). If a "ZONE LIST" is used as the “Stop” event, the device de-activates when all the zones in that list restore from a previous fault, trouble, or alarm condition. This occurs regardless of what is programmed to "START"...
Page 36
Choices for Start/Stop Zone Types and System Operations: 00 = No Response (Not Used) 22 = Disarming (Code + Off) 43 = Communication failure 01 = Entry/Exit #1 23 = No Alarm Response 44 = RF Low Battery 02 = Entry/exit #2 27 = Access Point (allows more than one 45 = Polling Loop Failure 03 = Perimeter...
Page 37
PROMPT EXPLANATION Enter 0 for V-Plex (polling loop) devices. Enter 1 for (ECP) relay modules (4204/4204CF). 02 RELAY TYPE Press [✱] to continue. V-PLEX For polling loop trigger outputs (4101SN), enter the protection zone number (001-032) linked to each output, 02 V-PLEX ZONE # if used.
Relay Voice Descriptors Each voice descriptor can consist of up to 3 words selected from the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list (later in this section). The index numbers from this vocabulary list are to be used for relay voice descriptors only. For normal system voice annunciation (e.g., alarms, troubles, status), use the highlighted words in the alpha vocabulary list in the Alpha Programming part of this guide.
Relay Voice Descriptors and Custom Word Substitutes Vocabulary Word Index Word Index Word Index Word Index Word Index Air ......116 Device ......060 Gas ......138 Off......011 Smoke ..... 024 Alarm ....... 255 Dim ......163 Glass......139 Office ....... 147 South.......
System Layout Worksheets Before programming any security system, you should first define the installation. To help you lay out a partitioned system, use the following worksheets. This will further simplify the programming process. PARTITIONS Partition # Descriptor (4-char max) Prim. Sub. # Sec.
Page 41
DEVICES (keypads, 4204, rf receivers, communicator) Sound Supv House Kypd Panel Addr Type Part Glbal Device Types: 00 = Device Not Used 01 = Alpha Console 03 = RF Receiver 04 = Output Relay Module 05 = Not Used 06 = Communicator 09 = Not Used 10 = Not Used Console Sounder Options:...
Page 44
ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 995, 996, and 999 Enter yes/no for each partition-field *22 Zone Zone Bell/Relay Report Zone Information and Type Activation Code Alpha Descriptor (3 words max.) (see note below) NOTE: Do Not Use Zone No. 995 in a Fire Alarm application. ZONE DEFINITIONS FOR SYSTEM ZONES;...
Page 45
ZONE DEFINITIONS FOR RELAY SUPERVISORY ZONES 601-632 Zone Information Zone Information Zone Zone Report Zone Zone Report Type Code Type Code Alpha Descriptor (3 words max.) Alpha Descriptor (3 words max.) NOTE: Only the relays on 4204CF modules may be supervised. If supervision is programmed for other types of Output Devices, unpredictable results may occur.
Page 46
ZONE DEFINITIONS FOR SUPERVISORY OF ECP DEVICE ZONES 800-830 Zone Information Zone Information Zone Zone Report Zone Zone Report Type Code Type Code Alpha Descriptor (3 words max.) Alpha Descriptor (3 words max.) Zone Types 00=zone not used 07=24-hour audible 16=fire w/verification 22=disarm 01=entry/exit 1...
Page 47
Output Devices Worksheets Applicable only if relays (4204/4204CF) or V-Plex are used. Output Devices – Programmed in the #93 Menu Mode in the Output Programming Section. Fill in the required data on the worksheet below and follow the procedure in the installation and setup guide as you enter the data during the displays and prompts that appear in sequence.
Page 48
OUTPUT DEVICES WORKSHEET (cont’d) S T A R T S T O P 0=V-Plex V-Plex Zone # Relay # for OUTPUT Relay 1=4204/ 4204/ Restrict DEV # Group 4204CF Dev Add 4204CF EV/ZL Zone ZT / P ZT / P 4204/4204CF —...
Page 49
OUTPUT DEVICES WORKSHEET (cont’d) S T A R T S T O P 0=V-Plex V-Plex Zone # Relay # for OUTPUT Relay 1=4204/ 4204/ Restrict DEV # Group 4204CF Dev Add 4204CF EV/ZL Zone ZT / P ZT / P 4204/4204CF —...
Page 50
OUTPUT DEVICES WORKSHEET (cont’d) S T A R T S T O P 0=V-Plex V-Plex Zone # Relay # for OUTPUT Relay 1=4204/ 4204/ Restrict DEV # Group 4204CF Dev Add 4204CF EV/ZL Zone ZT / P ZT / P 4204/4204CF —...
Page 51
A = DEVICE ACTION 0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off; 4 = Toggle alternately between START and STOP events EV = EVENT 0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble; 4 = Restore ZL = ZONE LIST 01-15, 00 = Not Used "START"...
Page 52
Zone List 5: Started or stopped by zone numbers (enter 000 to end entries). Zone List 6: Started or stopped by zone numbers (enter 000 to end entries). Zone List 7: Started or stopped by zone numbers (enter 000 to end entries). Zone List 8: Started or stopped by zone numbers (enter 000 to end entries).
Scheduling Menu Prompts To program schedules, enter Scheduling program mode by pressing [User Code] + # + 80 to display the first choice of the menu driven programming functions. NOTE: Only users with an Installer or Master level user code may enter the #80 mode. Press 0 (NO) or 1 (YES) in response to the displayed menu selection.
Scheduling Worksheets Time Windows Definitions Worksheet. The system provides 20 time windows that are defined with start and stop times. They are programmed in the #80 Menu Mode. Fill in the required data on the worksheet below and follow the procedure in the installation and setup guide as you enter the data during the displays and prompts that appear in sequence.
Page 55
Holiday Schedule Worksheet: The system provides up to 16 holidays that can be assigned for the system. Each holiday can be assigned to any combination of partitions. Fill in the required data on the worksheet below and follow the procedure in the installation and setup guide as you enter the data during the displays and prompts that appear in sequence.
Page 56
Automatic Refresh: The system automatically updates the status of all Time-Driven Events upon any of the following occurrences: • Changing of the time or date via #63 mode • Exiting #80 Scheduling Menu mode • Exiting Program mode • After a disconnect from the downloader •...
Page 57
Activation time: Refers to when the action is to take place relative to the time window. Beginning of time window End of time window During time window active period only (On at beginning of window, off at end). Limitation of Access Worksheet The system provides up to 8 Access Schedules that can be programmed for the system. Fill in the required data on the worksheet below and follow the procedure in the installation and set guide as you enter the data during the displays and prompts that appear in sequence.
Need help?
Do you have a question about the VISTA-32FB and is the answer not in the manual?
Questions and answers