Advertisement

4. List of Information

List of Information
INF
Description
Standard Information numbers in monitor direction
System Function
0
End of General Interrogation
0
Time Synchronization
2
Reset FCB
3
Reset CU
4
Start/Restart
5
Power On
Status Indications
16
Auto-recloser active
17
Teleprotection active
18
Protection active
19
LED reset
20
Monitor direction blocked
21
Test mode
22
Local parameter Setting
23
Characteristic1
24
Characteristic2
25
Characteristic3
26
Characteristic4
27
Auxiliary input1
28
Auxiliary input2
29
Auxiliary input3
30
Auxiliary input4
Supervision Indications
32
Measurand supervision I
33
Measurand supervision V
Phase sequence supervision
35
36
Trip circuit supervision
37
I>>backup operation
38
VT fuse failure
39
Teleprotection disturbed
46
Group warning
47
Group alarm
Earth Fault Indications
48
Earth Fault L1
49
Earth Fault L2
50
Earth Fault L3
51
Earth Fault Fwd
52
Earth Fault Rev
Contents
Transmission completion of GI items.
Time Synchronization ACK.
Reset FCB(toggle bit) ACK
Reset CU ACK
Relay start/restart
Relay power on.
If it is possible to use auto-recloser, this item is set active, if
impossible, inactive.
If protection using telecommunication is available, this item is
set to active. If not, set to inactive.
If the protection is available, this item is set to active. If not,
set to inactive.
Reset of latched LEDs
Block the 103 transmission from a relay to control system.
IECBLK: "Blocked" setting.
Transmission of testmode situation froma relay to control
system. IECTST: "ON" setting.
When a setting change has done at the local, the event is
sent to control system.
Setting group 1 active
Setting group 2 active
Setting group 3 active
Setting group 4 active
User specified signal 1 (Signal specified by IECB1: ON) (*1)
User specified signal 2 (Signal specified by IECB2: ON) (*1)
User specified signal 3 (Signal specified by IECB3: ON) (*1)
User specified signal 4 (Signal specified by IECB4: ON) (*1)
Zero sequence current supervision
Zero sequence voltage supervision
Negative sequence voltage supevision
Output circuit supervision
VT failure
CF(Communication system Fail) supervision
Only alarming
Trip blocking and alarming
A phase earth fault (*2)
B phase earth fault (*2)
C phase earth fault (*2)
Earth fault forward (*2)
Earth fault reverse (*2)
 292 
6 F 2 T 0 1 7 2
Type
GI
COT
FUN
ID
--
8
10
255
--
6
8
255
--
5
3
160
--
5
4
160
--
5
5
160
Not supported
1, 7, 9, 12,
GI
1
160
20, 21
Not supported
1, 7, 9, 12,
GI
1
160
20, 21
1, 7, 11, 12,
--
1
160
20, 21
GI
1
9, 11
160
GI
1
9, 11
160
Not supported
1, 7, 9, 11,
GI
1
160
12, 20, 21
1, 7, 9, 11,
GI
1
160
12, 20, 21
Not supported
Not supported
GI
1
1, 7, 9
160
GI
1
1, 7, 9
160
GI
1
1, 7, 9
160
GI
1
1, 7, 9
160
GI
1
1, 7, 9
160
Not supported
Not supported
GI
1
1, 7, 9
160
Not supported
Not supported
Not supported
GI
1
1, 7, 9
160
GI
1
1, 7, 9
160
GI
1
1, 7, 9
160
GI
1
1, 7, 9
160
GI
1
1, 7, 9
160
Not supported
Not supported