Installati n of Temperature Controller
WARNING
Turn the power off. Do not atte pt to connect the
temperature controller(s) with the power on.
Although the controller is a low voltage device, there
is 120 volt potenti l next to the temperature
controller connecti ns inside the unit.
Do not connect the temperature controller to the
120VAC terminals provided for the optional olenoid
drain valves.
Controller Loca on
The controller should be out of reach of small
children.
Avoid loca ons where the controller may become
hot (near an oven or radiant heater).
Avoid loca ons in direct sunlight. The digital
display may be di cult to read in direct sunlight.
Avoid loca ons where the temperature controller
could be splashed with liquids.
Do not install in loca ons where the controller
can be adjusted by the public.
Cable Lengths and Sizes
The cable for the temperature controller should be a
non-polarized two-core cable with a minimum gauge
of 22 AWG. The maximum cable length from each
controller to the water heater depends on the total
number of wired controllers connected to the water
heater.
Number of Wired Controllers
MC-195T Only
MC-195T, MC91-2
MC-195T, MC91-2, MC91-2
MC-195T, MC91-2, MC91-2, MC-91-2
Total Max.
Cable Length
82
(25 m)
164
(50 m)
164
(50 m)
164
(50 m)
KBP Series Manual
Downloaded from http://GadgetsGo.com Rinnai Authorized Dealer
Config ration
A maximum of 4 temperature controllers can be
installed for a water heater or bank of water heaters.
Controllers can only be wired in parallel. Controllers
cannot be wired in series.
MC-195T
Maximum 4 Controllers
Rinnai
Water
Heater
Wire controllers in parallel
The 4 temperature controllers can consist of one
MC-195T-US and no more than three MC-91-2
controllers.
MC-91-1 should not be installed on a unit that already
has an MC-91-2 connected.
Maximum 3 MC-91-2
49

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RUR98i and is the answer not in the manual?

Questions and answers

john
February 2, 2025

how to set water temperature

1 comments:
Mr. Anderson
February 10, 2025

If the Rinnai RUR98i has recirculation activated, the temperature may not be adjustable. The MC-195T-US controller allows configuration, but if the temperature is stuck at 120°F and the lock icon is not on, try power cycling the system for at least 15 minutes. If that does not work, consult the installer or check if recirculation settings are preventing temperature adjustments.

This answer is automatically generated

Table of Contents

Save PDF