(4)

Outdoor unit fan control

(a) Outdoor unit fan tap and fan motor speed
Model
100-140
200, 250
Notes (1) Fan motor speed for model 200 and 250 are same for both top and bottom lines
(2) Value in ( ) are for the model 125, 140.
(3) Value in ( ) are for the model 250.
(b) Fan tap control during Cooling/Defumidifying operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the higher.
zone
Tap 5
zone
Tap 5
zone
Tap 4
zone
Tap 3
zone
zone
15
18
(c) Fan tap control during heating operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the lower.
zone
Tap 3
zone
Tap 3
zone
Tap 4
zone
3
Outdoor air temp. (˚C)
(d) Outdoor unit fan control at cooling low outdoor air
1)
When all the following conditions are established after the start of compressor, the following control is implemented.
If the outdoor air temperature (Tho-A) is in the zone
seconds from the start of outdoor unit fan and the outdoor unit fan is at the tap 1 speed, the outdoor unit fan speed is
controlled according to the outdoor unit heat exchanger temperature (Tho-R1, R2).
Note (1) It is detected with Tho-R1 or R2, whichever the higher.
zone
5
Outdoor air temp. (˚C)
Mode
Cooling/Dehumidifying
Heating
Cooling/Dehumidifying
Heating
zone
zone
zone
Tap 5
Tap 5
Tap 5
Tap 4
(1)
Tap 4
Tap 3
(1)
Tap 3
Tap 2
zone
zone
46
48
30
37
Outdoor air temp. (˚C)
zone
zone
zone
Tap 3
Tap 4
Tap 4
Tap 5
(1)
Tap 5
Tap 6
zone
zone
12
15
9
zone
10
➀ speed ➁ speed ➂ speed ➃ speed ➄ speed ➅ speed ➆ speed
200
350
600
200
350
600
➀ speed ➁ speed ➂ speed ➃ speed ➄ speed ➅ speed ➆ speed
200
370
560 (600)
200
370
560 (600)
Note (1) If the "silent mode start" signal is received from the remote controller,
zone
the speed changes from Tap 4 to Tap 3.
Tap 4
Tap 3
Tap 2
Tap 1
zone
zone
20
30
Outdoor unit heat exchanger temp. (˚C)
Note (1) If the "silent mode start" signal is received from the remote controller, the speed changes
from Tap 4 to Tap 3.
zone
1
zone
-2
0
Outdoor unit heat exchanger temp. (˚C)
in the cooling/dehumidifying mode, it has elapsed 20
Retained
Outdoor unit fan speed
-1
-10min
20
Outdoor unit heat exchanger temp. (˚C)
319
-
-
Fan motor tap
740
820
870
740
820
870
820
850
910
(3)
820
850
910
(3)
zone
zone
43
53
33
40
zone
3
Outdoor unit fan speed
-1
+10min
30
'12 • PAC-T-174
-1
Unit: min
910 (950)
(2)
910 (950)
(2)
950
950