Installer Setup

Follow the procedure below to configure
the thermostat to match the installed
heating/cooling system, and customize
feature operation as desired.
To begin, press and hold the
buttons until the display changes.
• Press
to change settings.
t
• Press
to advance to next
s
function.
• Press and hold
save settings.

Setup function

1
System type
TH3110D only
5
Heating cycle rate
(CPH: cycles/hour)
TH3110D only
6
Auxiliary heat
cycle rate (CPH)
TH3210D only
8
Emergency heat
cycle rate (CPH)
TH3210D only
9
Compressor
cycle rate (CPH)
14 Temperature
display
15 Compressor
protection
Compressor Protection (Setup Function 15): Forces the compressor to wait a few minutes before
restarting, to prevent damage. During the wait time, the message Cool On or Heat On (heat pumps
only) will flash on the display.
and
s
t
to exit and
ts
Settings & options (factory settings in bold)
0
Gas, oil or electric heat with air conditioning
1
Heat pump (5 minute compressor off time in heating and cool-
ing)
5
For gas or oil furnaces of less than 90% efficiency
1
For steam or gravity systems
3
For hot water systems & furnaces of over 90% efficiency
9
For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
5
For gas or oil furnaces of less than 90% efficiency
1
For steam or gravity systems
3
For hot water systems & furnaces of over 90% efficiency
9
For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
9
For electric emergency heat
1
For steam or gravity systems
3
For hot water systems & furnaces of over 90% efficiency
5
For gas or oil furnaces of less than 90% efficiency
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
3
Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5, or 6 CPH]
0
Fahrenheit
1
Celsius
5
Five-minute compressor off time
[Other options: 0, 1, 2, 3 or 4-minute off time]
1
Function
number
5
Setup
0
Setting
MCR29402

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Pro 3000 Series and is the answer not in the manual?

Questions and answers

Sharon Burkhamer
January 17, 2025

when should the Emergency switch be used and with which **** setting?

1 comments:
Mr. Anderson
February 3, 2025

The Emergency Heat (em Heat) switch on the Honeywell Pro 3000 Series thermostat should be used only when your heat pump is not functioning or cannot efficiently heat your home. In this mode, the compressor is locked out, and the auxiliary heating system (e.g., electric or gas furnace) is used instead. This setting should be selected specifically for heat pumps with this capability.

This answer is automatically generated

Table of Contents

Save PDF