Mitsubishi Electric 9800A Series Owner Technical Manual page 8

Mitsubishi motors uninterruptible power supply system owners/technical manual
Hide thumbs Also See for 9800A Series:
Table of Contents

Advertisement

MITSUBISHI
ELECTRIC
This UPS does not include a Bypass input circuit breaker (MCCB) to
protect bypass circuit. The Bypass input circuit breaker (MCCB) is to be
field
supplied
Specifications are as follows:
Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac)
100
150
225
300
375
500
750
AC input and AC output overcurrent protection and disconnect devices shall be field
supplied and installed. The DC output MCCB shall be field supplied and installed. The
overcurrent protection device should be installed in the Battery cabinet and rated as
indicated in TABLE 1.4.
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
WARNING 2
and
installed.
Recommended
480
600
480
600
480
600
480
600
480
600
480
600
480
600
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page Number:
Breaker
(MCCB)'s
Breaker (A)
120
150
96
125
180
225
144
200
271
350
217
300
361
500
289
400
451
600
361
500
601
800
481
600
902
1200
722
900
1-2