Operating Instructions Fire alarm system EBL512 G3, V1.1.x
In case of a pre-warning, the following happens:
 The buzzer in the c.i.e. sounds 0.8 sec. each 5
sec.).
 Outputs programmed for pre-warning are activated.
 In the c.i.e. display, a presentation number (zone/address) is
shown (for the first pre-warning).
 In the c.i.e. display, a user definable text message (= the
alarm text for fire alarm) is shown (if programmed).
Example; pre-warning zone 123, address 45 (within zone 123):
Zone
123-45
User definable alarm text for 123-45.
Menu
"
SMOKE
" after the presentation number is automatically added
depending on the type of alarm point (i.e. SMOKE, HEAT, MULTI or
MCP).
NOTE! The text "
Menu
door in the CU is open.
If more than one pre-warning is activated, the LEDs "Alarms queued"
(L6) are blinking and the pre-warnings will be automatically scrolled
(each five seconds).
Pre-warnings are automatically reset see chapter "Alarm reset", page
49.

Fire alarm

The system can handle up to 15360 fire alarms but only 512 fire
alarms can be shown in the c.i.e. display. If more than 512 fire alarms
18
Outputs programmed for General pre-warning and outputs programmed
for the activated pre-warning(s).
39
Pre-warning
Address
" (P4) is visible in the display, only if the
th
sec. (0.8 / 5
18
SMOKE