Re-Connect Loop (H8/S2) - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
31.3
Action
"Menu"
"↵ "
Scroll to menu S2.
"↵ "
"↵ "
Depending on the
selected type, the
following will be
shown:
"↲ "
"ESC
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Re-connect loop (H8/S2)

Disconnected (disabled) loops / zone lines (via menu H8/S1) are
indicated by LED
and listed in menu H4/U1.
NOTE! When you re-connect a COM loop all the statistics shown in
menu H5/A7 will be erased and set to "0".
When all loops / zone lines have been re-enabled, The LED
"General disablements" (L10) will be turned OFF, if
Disablements
there are no other disablements in the system.
Text in display
S1 Disconnect loop / zone line input
S2 Re-connect loop / zone line input
S3 Acknowledge SERVICE signal
S4 Clear weekly average
S5 Test of alarm devices
S6 Safe shut down of control unit
S7 Activate address in alarm mode
S8 Synchronize the control units
S9 Change code for service / maintenance
S10 Change code for PC-communication
S2 Re-connect loop
Re-connect type:
COM-loop
Zone line input
Addr zone interface
Re-enable COM-loop: 0, control unit: 00
Re-enable zone line input
Zone line input: 0, exp board: 0, control unit: 00
Re-enable addressable zone interface
Input technical number: 000000
Re-connect type:
COM-loop
Zone line input
Addr zone interface
S2 Re-connect loop
"General disablements" (L10)
Fault / Disablements
131
Fault /
Comments
Procedure according to
chapter "Access code for
service / maintenance (H5
and H8)", see page 116.
"▲" or "▼" to
Use
select a type and press
"↵ ".
Write the required data and
press "↲ ".
Continue to re-connect or
press "ESC" to menu S2.
Scroll to another menu or
press "ESC".