D9412GV3/D7412GV3
v8.11 and Higher
Program Entry Guide
EN
Control Panels
Get other manuals https://www.bkmanuals.com

Advertisement

Table of Contents
loading

Summary of Contents for Bosch D9412GV3

  • Page 1 D9412GV3/D7412GV3 v8.11 and Higher Program Entry Guide Control Panels Get other manuals https://www.bkmanuals.com...
  • Page 2 Important Notes Corporation in the United States or in other countries. Molex is a registered trademark of Molex These notes should be heeded for Incorporated. successful operation and programming. Bosch Security Systems, Inc. | 10/11 | F01U170807-02 Get other manuals https://www.bkmanuals.com...
  • Page 3: Table Of Contents

    Route Group Parameters ......136 2.9.2 Area Text ........... 56 Miscellaneous .......... 137 2.10 User Interface ..........59 Cross Point Parameters ......139 2.10.1 Commands ..........60 ACCESS CONTROL ........ 140 Bosch Security Systems, Inc. | 10/11 | F01U170807-02 Get other manuals https://www.bkmanuals.com...
  • Page 4 Table 21: Verify Time .......... 39 Table 22: CF### Key Strokes ......58 Table 23: CF### Custom Function Keystrokes ... 58 Table 24: Keypad Programming Choices .... 60 Bosch Security Systems, Inc. | 10/11 | F01U170807-02 Get other manuals https://www.bkmanuals.com...
  • Page 5: 1.0 Introduction

    EN | 5 Table 2: Literature Referenced 1.0 Introduction Using this Program Entry Guide Document Name Part Number This guide is only for programming the D9412GV3 D1255 Installation Instructions 74-06819-000 and D7412GV3 Control Panels. D1256/D1257 Installation 74-06925-000 Although this guide specifically refers to the...
  • Page 6: Guide To Programming Options

    D9412GV3/D7412GV3 | Program Entry Guide | 1.0 Introduction EN | 6 Guide to Programming Options Full configuration of the control panel is only achieved through use of the Remote Programming Software (RPS). A limited keypad programmer’s mode is available to modify some of the more commonly changed parameters.
  • Page 7: Local Keypad Programming

    D9412GV3/D7412GV3 | Program Entry Guide | 1.0 Introduction EN | 7 1.2.1 Local Keypad Programming GV3 now offers a Local Keypad Programming menu with the Service Passcode only. It includes all custom options. For a list of program items you can set using Keypad Programming, refer to Figure 1 on page 7 and Figure 2 on page 8.
  • Page 8: Figure 2: D1260 Keypad Programming Menu And Page References

    D9412GV3/D7412GV3 | Program Entry Guide | 1.0 Introduction EN | 8 Figure 2: D1260 Keypad Programming Menu and Page References Refer to Phone # on page 12. Refer to Phone # Format on page 13. Refer to Enhanced Comm on pages 130 to 132.
  • Page 9: Table 3: Ul 864 Programming Requirements

    D9412GV3/D7412GV3 | Program Entry Guide | 1.0 Introduction EN | 9 Guide to UL 864 Programming Requirements This section identifies the programming requirements you must make in order to comply with UL 864 Commercial Fire applications. NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES This product incorporates field-programmable software.
  • Page 10 D9412GV3/D7412GV3 | Program Entry Guide | 1.0 Introduction EN | 10 Table 3: UL 864 Programming Requirements (continued) Product Feature/Option Permitted in Possible Settings Settings Permitted in Refer to UL 864? (Y/N) UL 864 Page: Bat Fail/Restoral Report Yes / No...
  • Page 11: Table 4: Ul 864 Programming Recommendations

    F01U143070) * Set the Path 1 Poll Rate to 65535 for 24 hr. The following programmable parameters are recommended by Bosch when installing a commercial fire alarm system. Always check with your local Authority Having Jurisdiction. Table 4: UL 864 Programming Recommendations...
  • Page 12: Guide To Ul 864 Programming Requirements

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 12 Phone # 2.0 Panel and Area Wide Parameters Default: Blank Selection: Up to 24 characters This section has twelve programming categories: 0 to 9 Numbers 0 through 9 ...
  • Page 13: When The Keypad Reads Parameter Saved, Your Selection Has Been Configured.2.2

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 13 If you program the primary phone number with a Keypad Programming of Phone # sequence to temporarily disable Call Waiting D1255 (typically *70 pause, but verify with the phone service 1.
  • Page 14: Phone Parameters

    Format Reports to the receiver. Point/User Flag selection has been configured. affects Bosch Modem IIIa Communication Format data as shown in Table 5. The Bosch Security D1260 Systems, Inc. D6500 or D6600 Receiver adds the 1. Refer to Figure 2 on page 8 to access Keypad...
  • Page 15: Special Point/User Reporting

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 15 2.2.1 Special Point/User Reporting Table 5: Modem IIIa Communication Format Independent Zone Control Notice: When using Data - User ID Numbers Independent Zone Controls (IZC) to send...
  • Page 16 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 16 Phone Supv Time Buzz on Fail Default: Default: Selection: Selection: 0, 10 to 240 Yes or No No phone line supervision. Generate panel-wide trouble tones...
  • Page 17: Routing

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 17 Routing Expand Test Report Use routing to select full or partial groups of events to Default: report to up to eight different destinations (four over phone, four over network).Routing includes choosing...
  • Page 18: Programming Primary And Backup Destinations

    2.3.4 Enhanced Routing digital reporting requirements for UL 864. Fire Alarm The D9412GV3 and D7412GV3 allow events to be Events have the highest priority and reports are sent sent to up to four additional SDI Paths. The network first for each group. Other events are sent in the...
  • Page 19 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 19 There are four Route Groups which contain a Keypad Programming of R# Primary Device selection of event categorizes and individual events. D1255 Each group has a primary and a backup device. The 1.
  • Page 20 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 20 R# Backup Device Refer to Section 5.5 Programming Path Numbers and IP Addresses for Enhanced Communications on Default: No Device page on page 131 to enable enhanced communication paths.
  • Page 21: Route Group Categories

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 21 2.3.9 Route Group Categories Burglar Reports Fire Reports Select Yes to send a report when the event occurs. Refer to Table 10 on page 21.
  • Page 22: Table 11: User Reports

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 22 Test Reports User Reports To meet UL 864 requirements for Selecting Yes enables a report to be sent when the Central Station and Remote Station event occurs.
  • Page 23: Table 12: Test Reports

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 23 Diagnostics Reports Table 12: Test Reports Selecting Yes enables sending a report when the event occurs. If the off-normal state of the events Report Selections...
  • Page 24: Table 13: Diagnostic Reports

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 24 Table 13: Diagnostic Reports (Continued) Table 13: Diagnostic Reports Report Selections Report Report Selections Report Description Description R# Rt Comm Rstl Yes, No Restoral of...
  • Page 25: Table 15: Auto-Function Reports

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 25 Table 16: RPS Reports When activating an on-board relay using remote automation software, the D9412GV3 and D7412GV3 Control Report Selections Report Description Panels log and print the resulting event...
  • Page 26: Table 17: Point Reports

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 26 User Chng Reports Point Reports Selecting Yes enables a report to be sent when the Selecting Yes enables a report to be sent when the event occurs.
  • Page 27: Event Priority

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 27 Access Reports Table 20:Event Descriptions, Priorities, and Numbers Selecting Yes enables a report to be sent when the event occurs. Event Event Access Granted, No Entry, Request to...
  • Page 28 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 28 Table 20: Event Descriptions, Priorities, and Table 20: Event Descriptions, Priorities, and Numbers (Continued) Numbers (Continued) Event Event Event Event Event Description Priority Number Event Description...
  • Page 29: Power Supervision

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 29 Power Supervision For the following items to be true, AC Fail/Restoral Report must be AC Fail Time programmed as Yes and AC Tag Along must be programmed as No.
  • Page 30: Printer Parameters

    Up to three D9131A Parallel Printer Interface Modules Be sure to program AC Fail/Restoral can be connected to the D9412GV3’s (one printer for Report as No if AC Tag Along is the D7412GV3’s) SDI bus. Each printer is identified by programmed Yes.
  • Page 31 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 31 P## Scope P## Fire Events Default: No Printer Default: Refer to the program record sheet Selection: Selection: No Printer, Area, Account, Panel Yes or No...
  • Page 32: Rps Parameters

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 32 2.6.2 Log Threshold Reports P## Point Event When the event log reaches the percentage Default: Refer to the program record sheet configured in Log % Full and the control panel is...
  • Page 33 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 33 The control panel continues to log events after the Log Keypad Programming of RPS Passcode Threshold Report is sent. When the event log reaches D1255 100%, a Log Overflow event is generated and the 1.
  • Page 34 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 34 RPS Call Back Program this item No if it causes false seizures of the phone line or if you do Default: not use RPS. This indicates that a...
  • Page 35: Select The Baud Rate For Rps-To-Control Panel

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 35 Keypad Programming of RPS PHONE # RPS Phone # D1255 Default: Blank 1. Refer to Figure 1 on page 7 to access Keypad Programming and navigate to the RPS...
  • Page 36: Miscellaneous

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 36 Miscellaneous Cancel Report Duress Type Default: Default: Selection: Yes or No Selection: 0, 1, 2, or 3 Send Cancel and Fire Cancel Reports according to routing.
  • Page 37 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 37 When the keypad reads PARAMETER SAVED, your Area 1 must be enabled: selection is configured.  System events such as power and 6. When the keypad reads AREA STATUS, press...
  • Page 38 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 38 Refer to the prompts P## Force Arm Returnable A# Auto Watch and P## Bypass Returnable in Section 3.2 Point Responses on page 91 for returning a point to the...
  • Page 39: Table 21: Verify Time

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 39 When the detector senses smoke or fire, the area’s When power restores to the points, the 60-sec sensor reset relay interrupts power to points confirmation window starts. If any detector, reset connected to it for the time in Verify Time.
  • Page 40 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 40 A# Area Type Default: Regular Selection: Regular, Master, Associate, or Shared Regular Arms or disarms as an independent area. Master Does not allow arming for this area unless all associate areas with the same A# account number are master exit delay armed or master armed.
  • Page 41: Shared-Area Characteristics

    Associate area keypads can show faults from shared areas as long as the shared The D9412GV3 and the D7412GV3 have two main areas fall within the scope of the associate area. types of annunciation: Fire Bell and Burg Bell. Both...
  • Page 42 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 42 Select the bell pattern this area uses to signal an A# Fire Time alarm on a Fire point. Default: 6 min When an alarm occurs on two Fire...
  • Page 43: Open/Close Options

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 43 Bell Test After Confirmation A# Single Ring In areas that send Opening and Closing Reports, the Default: Bell Test occurs after the control panel sends the...
  • Page 44 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 44 To suppress reports: A# Account O/C  Use Opening/Closing Windows to suppress Default: reports for a specified period of time and then automatically turn them on again.
  • Page 45 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 45 Determines if opening and closing activity is reported A# Area O/C when it occurs inside an Opening or Closing Window, as programmed in O/C Windows.
  • Page 46 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 46 A# Fail to Close A# Restrictd O/C Default: Default: Selection: Selection: Yes or No Yes or No Fail to Close Report is sent for this...
  • Page 47: Arming Features

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 47 To extend across midnight, you must use two A# Perimeter O/C windows:  Default: To suppress reports before midnight, use one window (for example, 20:00 start to 23:59 stop).
  • Page 48 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 48 Parameter Setup Requirement: When the first digit of the second code is pressed, the following message appears. As each digit is Two Man Rule can be completed only by entering pressed, an additional asterisk appears.
  • Page 49 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 49 Parameter Setup Requirement: To avoid the possibility of false alarms in Associate areas, do not use the A# Exit The Early Ambush timer can be started and stopped...
  • Page 50: Keypad (Command Center)

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 50 Keypad (Command Center) A# Entry Warning This programming module contains three Default: programming categories: Cmd Cntr Assignment, Area Text, and Custom Function. Selection: Yes or No 2.9.1...
  • Page 51 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 51 4. Press [NEXT]. The current keypad type shows CC# Supervised (for example, CC - 1 TYPE ENHANCED: YES). 5. Press [ENT] to change the keypad’s type.
  • Page 52 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 52 CC# A1 [through A#] in Scope CC# Scope Default: Refer to the preceding important Default: Refer to the program record sheet note Selection: Panel Wide, Custom, No Keypad,...
  • Page 53 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 53 CC# Enter Key Relay  The service passcode cannot be used for the CC# Enter Key Cycle Door Default: application. Selection: 0 to 128, A, B, C (0 to 64, A, B, C ...
  • Page 54 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 54 CC# Entry Tone  If a door is not programmed for this prompt and a door is not assigned to Default: the area using the D# Entry Area in...
  • Page 55 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 55 For SIA CP-01 Compliance CC# Passcode Follows Scope CC# Exit Tone can be set to Yes or No. Default: CC# Arm Now Warning Selection: Yes or No...
  • Page 56: Area Text

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 56 CC# Scroll Lock CC# Abort Display Default: Default: Selection: Selection: Yes or No Yes or No Prevents the idle system status text This keypad shows the Alarm from scrolling automatically.
  • Page 57 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 57 D1260 Series Keypad Area# Is On Although it is not programmed in this area, the D1260 Series keypad can display up to sixteen characters Default: Refer to the program record sheet for an Area Name on line 1 of its display.
  • Page 58: Figure 3: Softkey Locations On The D1260 Keypad

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 58 Custom Function Figure 3: Softkey Locations on the D1260 Keypad Default: Selection: 128 to 143 Enter the Custom Function number you want to program. You can program up to sixteen Custom Functions, which are numbered 128 to 143.
  • Page 59: 2.10 User Interface

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 59  128 to 143 Enable Custom Function 128 Custom function cannot be used to through 143 (Menu Function only): This change time (such as Daylight Saving function determines if a passcode is needed to Time).
  • Page 60: 2.10.1 Commands

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 60 2.10.1 Commands Master Arm Delay Similar to command initiation used in other Bosch Default: Security Systems, Inc. products, the Commands method provides continuity in the arming commands...
  • Page 61 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 61 Instant arms all perimeter points with point response Use this function to arm normal perimeter points and that starts an instant alarm (refer to P## Pt force-bypass faulted perimeter points, regardless of Response in Section 3.2 Point Responses on page...
  • Page 62: 2.10.3 Access Control Functions

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 62 View Memory Send Report Default: Default: Selection: Selection: -, E, or P -, E, or P Function Function Name Alternate Function Function Name Alternate Keystroke...
  • Page 63 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 63 Change Display Add User Default: Default: Selection: Selection: -, E, or P -, E, or P Function Function Name Alternate Function Function Name Alternate Keystroke...
  • Page 64 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 64 View Log User Cmd 9 Default: Default: Selection: Selection: -, E, or P -, E, or P Function Function Name Alternate Function Function Name Alternate...
  • Page 65 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 65 Reset Sensors Move to Area Default: Default: Selection: Selection: -, E, or P -, E, or P Function Function Name Alternate Function Function Name Alternate...
  • Page 66: 2.10.5 Configuration Authority

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 66 2.10.4 Custom Functions Default Text C Function 128 [through 143] Default: Default: Selection: -, E, or P Selection: -, E, or P Function Function Name...
  • Page 67: Keypad Programming Of The Keypad Programming

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 67 Keypad Programming of the Keypad Programming Table 25: Authority Level Selections Option D1255 Authority Description 1. Refer to Figure 1 on page 7 to access Keypad...
  • Page 68 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 68 L## Perimeter Delay L## Master Arm Delay Default: Refer to the program record sheet Default: Refer to the program record sheet Selection: - or E...
  • Page 69 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 69  If enabled in Routing, Walk Start and Walk End L## View Memory Reports are sent to the central station receiver at the beginning and end of the test.
  • Page 70 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 70 L## Cycle Door L## Send Report Default: Refer to the program record sheet Default: Refer to the program record sheet Selection: - or E Selection:...
  • Page 71: L## Secure Door-Door Mode Definitions

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 71 L## Access Control Level Table 26: L## Secure Door-Door Mode Definitions Default: Refer to the program record sheet Selection: - or E Door State Definition...
  • Page 72 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 72 L## Add User L## View Log Default: Refer to the program record sheet Default: Refer to the program record sheet Selection: - or E Selection:...
  • Page 73 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 73 L## Bypass a Point L## Move to Area Default: Refer to the program record sheet Default: Refer to the program record sheet Selection: - or E...
  • Page 74 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 74  Events print locally without alarm annunciation or L## Invisible Walk Test reporting to the central station receiver.  D1255 Keypad displays a sequential count and...
  • Page 75: 2.10.7 Access Control Levels

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 75 Custom Functions L## Send Duress L## C Function 128 [through 143] Default: Refer to the program record sheet Selection: - or E Default: Refer to the program record sheet...
  • Page 76 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 76 L## Disarm Level L## Function Level Default: Refer to the program record sheet Default: Refer to the program record sheet Selection: I, D, or -...
  • Page 77: 2.10.8 Sia Duress Passcode Options

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 77 2.10.8 SIA Duress Passcode Options 2.11 Function List USER INTERFACE Authority Levels L## The Function List is accessed when the user presses Disarm [MENU] (or the key corresponding to menu on the D1260) while the keypad shows the idle text.
  • Page 78: Relay Parameters

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 78  Relay Reports: When relay activity is reported to M## CC Address 1 [through 16] the receiver (refer to Section 2.3 Routing on page 17), on-board relays are reported as...
  • Page 79: 2.12.1 Area Relays

    Default: Alarm Bell Perimeter Fault Summary Fire Summary Trouble Selection: 0, 1 to 128 for D9412GV3, 1 to 64 Area Armed Reset Sensors for D7412GV3, A, B, or C Fire Bell AC Fail This voltage output relay activates and provides...
  • Page 80 Default: the following. Failure to do so causes TROUBLE PT ### for all point types 0, 1 to 128 for D9412GV3, 1 to 64 Selection: programmed as P## Resettable. for D7412GV3, A, B, or C ...
  • Page 81: 2.12.2 Panel-Wide Relays

    2.12.2 Panel-Wide Relays The following eleven relay options activate when they Default: occur anywhere in the control panel. They are not 0, 1 to 128 for D9412GV3, 1 to 64 Selection: restricted by area boundaries. for D7412GV3, A, B, or C...
  • Page 82: Passcode Or Token Worksheet

    Summary Fire Trouble Comm Fail Default: Default: Selection: 0, 1 to 128 for D9412GV3, 1 to 64 0, 1 to 128 for D9412GV3, 1 to 64 Selection: for D7412GV3, A, B, or C for D7412GV3, A, B, or C Activates when any Fire point in the control panel is Activates when a control panel cannot communicate in trouble, or if a Fire Supervision point is missing.
  • Page 83: User Groups

    User Groups When using the Add/Change User function at the keypad, the authority levels For the D9412GV3, there are 249 groups (99 groups and the changes made affect the master for the D7412GV3) consisting of one user with a passcode and token (master) and three users with user’s passcode and the entire group’s...
  • Page 84: Reporting And Logging

    D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 84 2.1.6 Reporting and Logging Phone # Format must be ModemIIIa for the following reports sent to the central station. Regardless of the reporting format, they log and print at the local printer as shown in Figure 4. Each sub-user is identified by the master user’s three-digit number plus an extension of 0, 1, 2, or 3.
  • Page 85 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 85 U### User Group User ### Default: Default: Selection: 000 or 001 to 249 (001 to 099 for Selection: 0, 1 to 8 the D7412GV3) Create a group of up to 249 users (99 for the D7412GV3) whose combinations can be enabled and Enter the User number you are programming.
  • Page 86 D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 86 U### Name Converting hexadecimal to decimal: If your card label contains letters as well as Default: Refer to the program record sheet numbers, the number is hexadecimal.*...
  • Page 87: 3.0 Points

    D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 87 Point Index 3.0 Points Default: Point Index Selection: 1 to 31 Use the point indexes to construct personality types The number of the point personality you are for points used in the system. The Index numbers are programming.
  • Page 88 D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 88 P ## Type Description Interior: Interior points are armed only by master arming the area. They are not armed when using Perimeter Arming functions. These points are typically used to monitor interior detection devices such as interior doors, motion detectors, photoelectric beams, and carpet mats.
  • Page 89 D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 89 P ## Type Description Keyswitch Maintained: Program P## Pt Response as 1. Do not connect initiating devices to a Keyswitch point. Normal: The area is disarmed. Short: A short is a trouble when the area is disarmed. A short is an alarm when the area is armed.
  • Page 90 D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 90 P ## Type Description Selection D279 (O/C Non-Priority): The D279 provides point arming and disarming independent of the area arm state. A non-priority D279 point arm state does not affect the area arm state. Point Response must be programmed 1.
  • Page 91: Point Responses

    D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 91 Alarm Verification: A Fire point can delay an alarm Point Responses by the length of time programmed in A# Verify Time 3.2.1 Applications for Point Responses 9, in the Area Parameters. Combined with A#...
  • Page 92 D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 92 P## Pt Response Default: Refer to the program record sheet Selection: 0 to F Controlled (Non-24-Hour Points) Point Response Armed Open Armed Short Disarmed Open Disarmed Short 24-Hour Points...
  • Page 93 D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 93 If you want this point to ring the bell P## Entry Tone Off because the message failed to reach the Default: central station receiver, program P## Audible After 2 Failures as Yes.
  • Page 94 D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 94 When a point programmed for P## Silent Bell is faulted, the timer for the A# Burg Time starts, even though the bell is not yet ringing. As much as 3 min can elapse before the second attempt fails.
  • Page 95 D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 95 P## Buzz On Fault Default: Selection: 0 to 3 Selection Operation for Controlled Points Operation for 24-hour, Fire and Aux AC Supervision Points (Point Types 0 and (Point Types 1, 2, and 3)
  • Page 96 Use this option to cause a relay (1 to 127 for * Transmission of Restoral Reports continues if the alarm, D9412GV3; 1 to 64 for D7412GV3) to respond when trouble, or bypass (by Sked, RPS, or Swinger bypass) a corresponding point with the same number (1 to condition occurred when the area disarmed, and the point restored.
  • Page 97 D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 97 Local While Disarmed suppresses all Local While Armed suppresses all reports reports from 24-hour points. Do not use from 24-hour points. Do not use P## Type P## Type 0 for this prompt. Remember 0 for this prompt.
  • Page 98: Bypassing A Point

    D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 98 Bypassing a 24-hour point: When a 24-hour point or P## Bypass Returnable 24-hour Supervisory point is bypassed, 24 HOUR BYPASS scrolls continuously at the keypad. Default: Bypassing a Fire Point: FIRE BYPASS scrolls to...
  • Page 99 D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 99 P## Swinger Bypass P## Defer Bypass Report Default: Default: Selection: Yes or No Selection: Yes or No Enable Swinger Bypass for this point. Send a Point Bypass Report with the...
  • Page 100 D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 100 The Cross Point feature does not activate when a P## Alarm Verify fault occurs on Controlled points (Point Types 1, 2 and 3) in the disarmed, entry delay, or exit delay...
  • Page 101: Point Assignments

    These entries assign point indexes to Points 1 to 127, points with P## Resettable programmed 129 to 247 for the D9412GV3 and Points 1 to 75 for as Yes. During the 5-sec reset time, the D7412GV3, and assign the points to the areas.
  • Page 102 D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 102 Keypad Programming of P### Point Index P### Debounce D1255 Default: 1. Refer to Figure 1 on page 7 to access Keypad Selection: 1 to 15 Programming and navigate to the POINT PARAMETERS option.
  • Page 103: P### Relay Codes/Relays

    D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 103 P### Point Text P### Relay Default: Refer to the program record sheet Default: Refer to the program record sheet Up to sixteen alphanumeric Selection: 0 to 8 Selection: characters Use this option to activate a relay when the point is Enter alphabetic characters (A to Z) in capital letters.
  • Page 104: Command 7 And Command 9

    Refer to the D9210B Program Entry Default: Guide (P/N: 32207). Selection: 0 to 8 This entry selects a relay (73 to 80 on the D9412GV3 CMD7 Relay or 9 to 16 on the D7412GV3) when COMMAND 9 is Default: P### Relay...
  • Page 105: Schedules (Skeds)

    D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 105 4.0 Schedules (Skeds) Table 29: Window Selections Windows Selection Sked Window Sked # Windo Use this programming module to define the windows for Opening and Closing and User Access.
  • Page 106 D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 106  If Disable O/C in Window is set to No and the W# Monday area is disarmed at any time, an Opening Event is sent without an Early to Open or Late to Open Default: modifier.
  • Page 107: Figure 5: Example Opening Window Timeline (Using Two Opening Windows On Same Day)

    D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 107 W# Open Window Start Make time entries using a 24-hour clock. For example: Default: 00: 00 Midnight is entered as 00:00 Selection: HH:MM (hours and minutes) 7:00 AM is entered as 07:00...
  • Page 108: Programming For Two Same Day Opening Windows (Refer To Figure 5) . 108 Programming To Link Two Days Over Midnight

    D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 108 Table 30: Programming for Two Same Day Opening Windows (refer to Figure 5) Open Close Early Early eXcept On Holiday Day of Week Begin Start Stop Begin Start...
  • Page 109: Programming Example: Linking Two Closing Windows Over Midnight

    D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 109 If the window must activate on the same day as it is W# Close Window Stop programmed, reboot the control panel to activate the window immediately. Default: 00: 00...
  • Page 110 D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 110 W# Xept Holiday W# Holiday 1 Default: Default: Selection: Yes or No Selection: Yes or No Do not activate this window on Use Holiday Index 1 with this holidays.
  • Page 111: Worksheet

    D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 111 Table 33: Opening and Closing Windows Worksheet Open Close eXcept Early Early Holiday Day of Week Holiday Index Area(s) Begin Start Stop Begin Start Stop S M T W T F S...
  • Page 112: User Group Windows

    D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 112 Table 36: Delivery Schedule* Open Close eXcept Early Early Holiday Day of Week Begin Start Stop Begin Start Stop Holiday Index Area(s) S M T W T F S...
  • Page 113 D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 113 UW# Sunday UW# Group Enable Default: Default: 00:00 Selection: Yes or No Selection: HH:MM (hours and minutes) This prompt, and the next six day of the week prompts, select the days of the week that the User This prompt must be programmed if this Group Window is active.
  • Page 114: Schedules (Skeds)

    D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 114 Each sked can be programmed with up to four 4.1.3 Holiday Indexes for User Group Windows Holiday Indexes. The Holiday Indexes can execute You can enable up to four Holiday Indexes to use with the sked on the holidays as well as on the date or User Group Windows.
  • Page 115 D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 115 Default: Selection: 0 to 24, 28, 29 Arm Area: This function simulates Arm Area #. S## Area 1[through #] the Master Arm Delay keypad Do not arm Default: No function.
  • Page 116 D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 116 Default: Selection: 0 to 24, 28, 29 Unbypass All Points: This function Unbypass all S## Area 1[through #] is not available as a keypad function. points in Area #.
  • Page 117 D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 117 Default: Selection: 0 to 24, 28, 29 Test Report: This function emulates Defer the Test S## Defer Test the Test Report? sub-function of the Report. Send Report? keypad function...
  • Page 118 D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 118 Default: Selection: 0 to 24, 28, 29 Execute Custom Func: This Blank No keypad is S## Cmd Center function emulates any of the custom specified for functions assigned to the keypad...
  • Page 119 The D9412GV3 supports eight doors; the D7412GV3 supports two doors. To regulate a user’s access for certain doors, assign the user a different authority level # with the same authority functions enabled.
  • Page 120 D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 120 Default: Selection: 0 to 24, 28, 29 Access Control Level Off: Turn off access for S## Access Ctl Level # This function emulates the level #. Default: No...
  • Page 121 D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 121 Default: Selection: 0 to 24, 28, 29 Access Authority Events Disable the S## Door 1 [through 8] Off: The control panel can log sending of Access Access Granted Events when...
  • Page 122 D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 122 Non-Expanded Off-Normal Test Report: Non-Expanded Off-Normal Test Report Events are only sent when any point is in the off-normal state from any area, but only sends the Off Normal Test Report Event.
  • Page 123 D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 123 S## Monday S## Time Default: Default: 00:00 Selection: Yes or No Selection: HH:MM (hours and minutes) S## Tuesday Enter the time that the sked executes. Make entries using a 24-hour clock (for example, 7:00 AM is Default: entered as 07:00, 2:45 PM is entered as 14:45).
  • Page 124: Holiday Indexes

    To delete the date completely, select No for all of the Holiday Index # entries. Holiday Index # Default: None Selection: Select Dates from the Calendar Bosch Security Systems, Inc. | 10/11 | F01U170807-02 Get other manuals https://www.bkmanuals.com...
  • Page 125: 5.0 Auxparm

    D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 125 SDI Automation 5.0 AUXPARM SDI automation defines the characteristics of a serial interface module (SIM) when used with home or Introduction business automation software. The SIM is a two-way...
  • Page 126: Sdi Rps Parameters

    D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 126 Status Rate SDI RPS Parameters Default: Configure remote programming software (RPS) parameters when communicating over a private local- Selection: 0 to 255 area network (LAN), wide-area network (WAN), or Status information is sent only when general packet radio system (GPRS).
  • Page 127: Configuration For Rps Over Network

    D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 127 RPS Address Verification 5.4.1 Configuration for RPS Over Network COMMAND 43 (Remote Programming) can establish Default: communication with RPS over the phone or over the Selection: Yes or No network.
  • Page 128: Figure 6: Command 43 Flow Chart (D1255)

    D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 128 Figure 6: COMMAND 43 Flow Chart (D1255) Command 43, Remote Program idle text (Area Name) (area text) <Help? Menu> Command key pressed *System Command* 43 pressed Enter choice: Enter choice: Select RPS via Phone>...
  • Page 129: Figure 7: Command 43 Flow Chart (D1265)

    D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 129 Figure 7: COMMAND 43 Flow Chart (D1265) Idle text COMMAND 43 RPS VIA PHONE ? NEXT NEXT RPS VIA NETWORK? NEXT ALLOW ANSWER ? USE PORT ##### ? (or ringing)
  • Page 130 D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 130 7. When the keypad reads RPS IP ADDRESS, press RPS IP Address # [NEXT] to advance to the RPS IP PORT option. The keypad shows the currently configured port Default: 0.0.0.0...
  • Page 131: Programming Path Numbers And Ip Addresses For Enhanced Communications

    D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 131 Programming Path Numbers and 3. Press [NEXT] or [PREV] to toggle to YES to enable enhanced communication or No to disable IP Addresses for Enhanced enhanced communication, and then press [ENT].
  • Page 132 D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 132 Refer to Keypad Programming of Path # IP Address, The value programmed in Path # Poll Rate is the Path # Port Number, and Path # Poll Rate on page interval at which the control panel sends a Heartbeat 132.
  • Page 133 D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 133 8. The keypad shows the currently configured IP 9. The Backspace softkey allows you to erase address. Press [NEXT]. The currently configured characters. The Clear softkey allows you to clear port number shows.
  • Page 134: Figure 8: Poll Rate Timeline

    D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 134 When the control panel first powers up, the first Heartbeat Poll for Path 1 is sent and is acknowledged in 1 sec. 120 sec after the first Heartbeat Poll is sent, the second Heartbeat Poll for Path 1 is generated and sent to the central station receiver.
  • Page 135: Ant-Replay Security Feature

    D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 135 Example of Retry Count: Path # Retry Count An acknowledgment of the heartbeat was not Default: received within 10 sec. The control panel sends the next Heartbeat Poll after the first 10-sec ACK wait...
  • Page 136: Route Group Parameters

    D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 136 This item determines whether the NIM is supervised. RG# Same Network Receiver If the NIM is supervised, disconnecting it from the control panel creates a Trouble SDI 88 Event and the...
  • Page 137: Miscellaneous

    D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 137 If a second passcode is not entered within the Miscellaneous programmed time, a Duress event is generated based on the first user code. Duress reports must be Fire Summary Sustain enabled in Routing in order to be sent to a central station.
  • Page 138 D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 138 When a point has P# Swinger Bypass set to Yes, For SIA CP-01 Compliance: the value set in Swinger Count determines the Abort Window is a required parameter. number of times the point is faulted erroneously within an hour before it is automatically bypassed.
  • Page 139: Cross Point Parameters

    There are 31 Cross Point Groups in the D9412GV3 Early Armed Relay and ten in the D7412GV3. Each Cross Point Group...
  • Page 140: 6.0 Access Control

    The D# Entry Area # prompt for the conditions. It does not apply to supervisory or trouble D9412GV3 is limited to the first 8 areas. conditions. Points programmed with point response D (Delayed) eventually enter into an alarm condition if the area is not disarmed in time.
  • Page 141: Effects Of Programming On Custom Function Activation

    D9412GV3/D7412GV3 | Program Entry Guide | 6.0 ACCESS CONTROL EN | 141 If D# Disarm On Open is set to Yes for the same All SDI devices, regardless of area door, and L## Function Level? is set to D or C, the...
  • Page 142 D9412GV3/D7412GV3 | Program Entry Guide | 6.0 ACCESS CONTROL EN | 142 Door points must be programmed as D# Auto Door? Perimeter points. If a 24-hour point type is required for the Door point, you can Default: use a Perimeter point type with a point...
  • Page 143: Strike Profile

    D9412GV3/D7412GV3 | Program Entry Guide | 6.0 ACCESS CONTROL EN | 143 Strike Profile This command unlocks the door This programming category is used to create a regardless of the armed state. specific door profile for:  Strike and shunt times.
  • Page 144 D9412GV3/D7412GV3 | Program Entry Guide | 6.0 ACCESS CONTROL EN | 144 D# Buzz Time D# Deactivate On Open? Default: Default: 2 sec Selection: Yes or No Selection: 0 to 240 sec Strike deactivates when the door is Buzz Time is not programmed for opened after a valid Access Granted this door.
  • Page 145: Event Profile

    D9412GV3/D7412GV3 | Program Entry Guide | 6.0 ACCESS CONTROL EN | 145 D# REXShunt Only? D# Access Granted? Default: Default: Selection: Yes or No Selection: Yes or No Programmed shunt time activates Access Events from this door so the door can be manually controller are sent to the control opened.
  • Page 146 D9412GV3/D7412GV3 | Program Entry Guide | 6.0 ACCESS CONTROL EN | 146 D# Enter Request? Default: Selection: Yes or No A Door RTE Event from this door controller is sent to the control panel for processing. A Door RTE Event from this door controller is not sent to the control panel for processing.
  • Page 147: 7.0 Sia Cp-01 Quick Reference

    D9412GV3/D7412GV3 | Program Entry Guide | 7.0 SIA CP-01 Quick Reference EN | 147 7.0 SIA CP-01 Quick Reference Table 40: Programming the Control Panels for SIA CP--01 Compliance Prompt Name Bosch Recommended Settings Shipping Default References for SIA CP-01 Compliance...
  • Page 148: Programming Prompts Directory

    D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory EN | 148 Programming Prompts Directory Panel and Area Wide Parameters ....12 P## Burglar Event ......31 Phone ............12 P## Access Event ......31 Phone # ..........12 P## User Event ........31 Phone Parameters........
  • Page 149 D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory EN | 149 Open/Close Options ......43 Custom Function ........ 58 A# Account O/C ......... 44 CF### Text ........58 A# Area O/C ........45 CF### Key Strokes ......58 A# Disable O/C in Window....45 User Interface...........
  • Page 150 D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory EN | 150 Authority Level ........67 L## Area O/C ........75 L## Disarm ........67 L## Restricted O/C......75 L## Master Arm Delay ....... 68 L## Perimeter O/C ......75 L## Master Arm Instant L## Send Duress........
  • Page 151 D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory EN | 151 U### User Group....... 85 P### Point Text........ 103 U### Area 1 [through Area #] Auth ..85 COMMAND 7 and COMMAND 9.... 104 U### Name........86 CMD7 Point Index ......104 U### Mstr Site ........
  • Page 152 D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory EN | 152 UW# Xept Holiday......114 Supervise SDI 80 ......125 UW# Holiday 1 [through 4] ....114 Schedules (Skeds) ........ 114 Status Rate ........126 Sked Number........114 SDI RPS Parameters......126 S## TimeEdit ........
  • Page 153 D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory EN | 153 Strike Profile .......... 143 Door # ..........143 D# Strike Time ......... 143 D# Shunt Time ......... 143 D# Buzz Time ........144 D# Extend Time ....... 144 D# Deactivate On Open? ....
  • Page 154 Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY, 14450 www.boschsecurity.com © Bosch Security Systems, Inc. 2010 Get other manuals https://www.bkmanuals.com...