Item
Pipe
Indoor fan
and
exhaust
fan
Heat
exchanger
core
Issue 04 (2022-06-30)
Baseline Requirement
The operating compressor
generates no metal friction
noise or collision noise from
inside.
The refrigerant pipe does
not leak or corrode, and the
wrapped thermal insulation
foam is intact.
Wear protective gloves and
touch the needle valve, and
soldering points in the
refrigerant pipe to check
whether there are oil stains.
No water exists under the
water pipe or on the
thermal insulation foam.
The refrigerant pipe support
is secure and intact.
The indoor fan and exhaust
fan guards are not
deformed, and the fan
blades are not damaged.
The indoor fan and exhaust
fan run smoothly.
The screws on the indoor
fan and exhaust fan are not
loose or distorted.
Check whether the heat
exchanger core is damaged.
Copyright © Huawei Technologies Co., Ltd.
8 System Operation and Maintenance
Troubleshooting
Replace the compressor.
Repair the leakage points and re-
wrap thermal insulation foam.
If there are oil stains, check whether
the suction and discharge pressure
of the compressor is within the
normal ranges. If the pressure is
beyond the normal range, contact
technical support.
● If drops of water are evenly
distributed, wipe off them with a
dry cloth.
● If there are large water marks,
close the water inlet sluice and
process the leak points. If the
thermal insulation foam is
damaged or missing, lay out new
thermal insulation foam.
Replace the refrigerant pipe support
and secure it again.
Replace the fan.
Take out the foreign matter.
Tighten the screws using a 10#
socket wrench.
If the heat exchanger core is
seriously damaged, replace it.
110