10. PROFIBUS Local/Remote Operation

The example below shows how to configure the VF-MB1/S15/AS3 for local/remote
operation.
<Terminal function>
F terminal ............ RUN command
R terminal ............ Local (Terminal in this example) / PROFIBUS switching
VIA(VF-MB1/S15) / RR(VF-AS3) terminal .... Operation frequency command
<Wiring>
<Parameter setting>
cmod
fmod
f112
<Operation>
R-CC terminal open:
R-CC terminal closed:

11. GSD file

As for acquisition of a GSD file for VF-MB1, VF-S15 and VF-AS3, please contact your
Toshiba distributor.
Variable resistor for adjustment
10k ohm
Operation command
Local/PROFIBUS
(command mode selection) = 0 (terminal board)
(frequency setting mode selection 1) = 1 (VIA(VF-MB1/S15) / RR(VF-AS3))
(input terminal selection 2 (R)) = 48 (Local/PROFIBUS control)
VF-MB1/S15/AS3 is controlled as slave device of PROFIBUS.
F-CC terminal short to RUN
F-CC terminal open to STOP
Output frequency is set up by the VIA(VF-MB1/S15) / RR(VF-AS3)) signal input.
- 44 -
Switch
E6581738④
VF-MB1/S15/AS3
PP
VIA(VF-MB1/S15)
RR(VF-AS3)
CC
SW1
F
SOURCE
SINK
R
P24
OUT