Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

NOTICE
Device failure due to overtemperature caused by faulty wiring
During operation, Active Interface Modules require a signal to terminal X609:9 and X609:10
for fan activation. If this signal is not present during operation, the fans do not rotate and
the module is shut down on overtemperature.
• Connect the signals to terminal X609:9 and X609:10 on the Active Interface Module
4.7.3.7

Meaning of the LED on the Voltage Sensing Module (VSM) in the Active Interface

Module

Table 4- 36
Description of the LED on the Voltage Sensing Module (VSM) in the Active Interface Module
LED
Color
RDY
---
Green
Orange
Red
Green/red
Green /
orange
or
red / orange
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Chassis-2 to control the fan.
State
Description
Off
The electronics power supply is missing or out of tolerance.
Continuous
The component is ready for operation and cyclic DRIVE-CLiQ communication is
light
taking place.
Continuous
DRIVE-CLiQ communication is being established.
light
Continuous
This component has at least one fault.
light
Remark:
The LED is activated irrespective of whether the corresponding messages have
been reconfigured.
Flashing 0.5
Firmware is being downloaded.
Hz
2 Hz flashing
Firmware download is complete. Waiting for POWER ON.
light
2 Hz flashing
Component recognition via LED is activated (p0144).
light
Remark:
Both options depend on the LED status when module recognition is activated via
p0144 = 1.
Line-side power components
4.7 Active Interface Modules Chassis-2
111