GE 489 Instruction Manual page 166

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

6.3 MEMORY MAP
Table 6–1: 489 MEMORY MAP (Sheet 12 of 29)
ADDR NAME
13A2
TACHOMETER ALARM
13A3
ASSIGN ALARM RELAYS (2-5)
13A4
TACHOMETER ALARM SPEED
13A5
TACHOMETER ALARM DELAY
13A6
TACHOMETER ALARM EVENTS
13A7
TACHOMETER TRIP
13A8
ASSIGN TRIP RELAYS (1-4)
13A9
TACHOMETER TRIP SPEED
13AA
TACHOMETER TRIP DELAY
DIGITAL INPUTS / WAVEFORM CAPTURE
13C0
ASSIGN DIGITAL INPUT
DIGITAL INPUTS / GND. SWITCH STATUS
13D0
ASSIGN DIGITAL INPUT
13D1
GROUND SWITCH CONTACT
OUTPUT RELAYS / RELAY RESET MODE
1400
R1 TRIP
1401
R2 AUXILIARY
1402
R3 AUXILIARY
1403
R4 AUXILIARY
1404
R5 ALARM
1405
R6 SERVICE
CURRENT ELEMENTS / OVERCURRENT ALARM
1500
OVERCURRENT ALARM
1501
ASSIGN ALARM RELAYS (2-5)
1502
OVERCURRENT ALARM LEVEL
1503
OVERCURRENT ALARM DELAY
1504
OVERCURRENT ALARM EVENTS
CURRENT ELEMENTS / OFFLINE O/C
6
1520
OFFLINE OVERCURRENT TRIP
1521
ASSIGN TRIP RELAYS (1-4)
1522
OFFLINE OVERCURRENT PICKUP
1523
OFFLINE OVERCURRENT TRIP DELAY
CURRENT ELEMENTS / INADVERTENT ENERG.
1540
INADVERTENT ENERGIZE TRIP
1541
ASSIGN TRIP RELAYS (1-4)
1542
ARMING SIGNAL
1543
INADVERTENT ENERGIZE O/C PICKUP
1544
INADVERTENT ENERGIZE PICKUP
CURRENT ELEMENTS / PHASE OVERCURRENT
1600
PHASE OVERCURRENT TRIP
1601
ASSIGN TRIP RELAYS (1-4)
1602
ENABLE VOLTAGE RESTRAINT
1603
PHASE OVERCURRENT PICKUP
1604
CURVE SHAPE
FLEXCURVE TRIP TIME AT 1.03 × PU
1605
FLEXCURVE TRIP TIME AT 1.05 × PU
1606
FLEXCURVE TRIP TIME AT 1.10 × PU
1607
FLEXCURVE TRIP TIME AT 1.20 × PU
1608
FLEXCURVE TRIP TIME AT 1.30 × PU
1609
FLEXCURVE TRIP TIME AT 1.40 × PU
160A
FLEXCURVE TRIP TIME AT 1.50 × PU
160B
FLEXCURVE TRIP TIME AT 1.60 × PU
160C
FLEXCURVE TRIP TIME AT 1.70 × PU
160D
1, 2, 3
See Table footnotes on page 6–39
6-22
RANGE
0 to 2
1 to 4
101 to 175
1 to 250
0 to 1
0 to 2
0 to 3
101 to 175
1 to 250
0 to 7
0 to 7
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 2
1 to 4
10 to 150
1 to 2500
0 to 1
0 to 2
0 to 3
5 to 100
3 to 99
0 to 2
0 to 3
0 to 1
5 to 300
50 to 99
0 to 2
0 to 3
0 to 1
15 to 2000
0 to 13
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
489 Generator Management Relay
6 COMMUNICATIONS
STEP
UNITS
FORMAT
1
F115
1
F50
1
%Rated
F1
1
s
F1
1
F105
1
F115
1
F50
1
%Rated
F1
1
s
F1
1
F210
1
F210
1
F109
1
F117
1
F117
1
F117
1
F117
1
F117
1
F117
1
F115
1
F50
× FLA
1
F3
1
s
F2
1
F105
1
F115
1
F50
× CT
1
F3
1
Cycles
F1
1
F115
1
F50
1
F202
× CT
1
F3
× Rated V
1
F3
1
F115
1
F50
1
F103
× CT
1
F3
1
F128
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
1
ms
F1
GE Power Management
DEFAULT
0
16
110
1
0
0
1
110
1
0
0
0
0
0
0
0
0
0
0
16
101
1
0
0
1
5
5
0
1
0
5
50
0
1
0
1000
0
65535
65535
65535
65535
65535
65535
65535
65535
65535