Siemens SINAMICS S120 System Manual page 210

Hydraulic drive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Hardware
6.2 Interfaces
Pin assignment of the pressure sensors at the module side
Table 6- 7
210
X251: Pressure sensor connection, channels X and Y
PIN
Signal name
1
P26.5DSY
2
P26.5DSX
3
-
4
-
5
MX
6
-
7
-
8
-
9
MY
10
MHY
11
PISTYN2
12
PISTYP2
13
MHX
14
PISTXN1
15
PISTXP1
Function
Pressure sensor Y:
supply voltage +26.5 V
Pressure sensor X:
supply voltage +26.5 V
Not assigned
Not assigned
Pressure sensor X:
supply voltage ground
Not assigned
Not assigned
Not assigned
Pressure sensor Y:
supply voltage ground
Auxiliary pin Y: Ground
Pressure sensor Y:
analog pressure actual value signal, refer-
ence potential
Pressure sensor Y:
analog pressure actual value signal, 0 ...
+10 V
Auxiliary pin X: Ground
Pressure sensor X:
analog pressure actual value signal, refer-
ence potential
Pressure sensor X:
analog pressure actual value signal, 0 ...
+10 V
System Manual, 04/2015, 6SL3097-4BA00-0BP1