SINAMICS G130
Engineering Information
Terminal block on the TM31 Terminal Module
Factory setting
-X520
Optocoupler inputs connected to common
potential
DI0
Not assigned
DI1
Not assigned
DI2
Not assigned
DI3
Acknowledge fault
-X530
Optocoupler inputs connected to common
potential
DI4
OFF 2
DI5
OFF 3
DI6
External fault
DI7
Not assigned
-X541
Bidirectional inputs/outputs
DI/DO8
Message: Ready to start
DI/DO9
Not assigned
DI/DO10
Not assigned
DI/DO11
External alarm
-X542
Relay outputs (changeover contact)
DO0
Inverter enable (Run)
DO1
Checkback signal No converter fault
-X521
Analog inputs, differential
AI0+
Not assigned
AI0-
AI1+
Not assigned
AI1-
-X522
Analog outputs
AO 0V+
AO 0-
Analog output, actual speed value
AO 0C+
AO 1V+
AO 1-
Analog output, actual motor current value
AO 1C+
-X522
Thermistor protection
+Temp
-Temp
The factory settings of the bidirectional inputs/outputs are underscored.
1)
A jumper must be inserted here if these inputs are not used
SINAMICS Engineering Manual – November 2015
290/528
Ó Siemens AG
1)
1)
1)
1)
Comment
Immediate pulse disable, motor coasts to standstill
Ramp-down along quick-stop ramp, only of relevance in
conjunction with the Braking Module
Factory-set as input
Factory-set as input
Factory-set as input
The factory setting for the outputs is 0 to 10 V.
The factory setting for the outputs is 0 to 10 V.
Input for KTY84 or PT1000 temperature sensor or PTC
thermistor