Troubleshooting
Error Code
Recovery Procedures
FB6 Error in position control loop
There is no change in the actual position even though the analog voltage
(setpoint speed) exceeds 5 V. The current operation is aborted and mode 4
(follow-up mode) automatically started. In follow-up mode, the position
controller is off. Follow-up mode can be terminated at any time. The
position controller is then reenabled.
Possible causes:
-
Encoder not connected, incorrectly connected or defective
-
The module's analog output is not wired
-
The power section is not switched on or not enabled
-
The axis is blocked by an obstacle of some kind or is jammed.
FB7
PLC failure
FB8
Invalid path specification
FB9
Invalid tool offset
FBA
Invalid G function for dimensional unit "degrees"
FBB
Path specification not in BCD code
FBC
EEPROM not programmable!
FBD
EEPROM failure!
FBE
No data in EEPROM/RAM !
FD0
Only one continuous loop permitted
FD1
No end of loop