Siemens Sinamics s120 Commissioning Manual page 131

With starter
Hide thumbs Also See for Sinamics s120:
Table of Contents

Advertisement

What?
5.7
Configuration,
summary
5.8
Configuring drive
functions
5.9
Summary
Note
The reference parameters and limit values can be protected from being automatically overwritten in the STARTER com-
missioning tool by p0340 = 1: Drive -> Configuration-> "Reference parameters / blocked list" tab.
6
Enable signals
and BICO inter-
connections
6.1
Line contactor
7.
Save the parame-
ters on the device
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
3.5 Commissioning the servo control booksize format for the first time
How?
The configuration of the drive train has been completed. A sum-
mary is displayed.
1. Click "Complete".
1. In the project tree click Drives\Drive xy\Configuration.
2. Click the "Function modules/technology packages" button.
Under the "Function modules" tab, you can activate single or
multiple function modules.
3. Click "OK".
The drive data can be copied to the clipboard for system docu-
mentation purposes and then pasted into a text processing pro-
gram, for example.
The enable signals for the infeed and the two drives must be
implemented via the digital inputs on the Control Unit.
1. Make the following settings for the line contactor:
p0728.8 = 1, sets DI/DO as output
p0738 = 0863.1 line contactor on
p0860 = 0723.9 line contactor, feedback signal
1. Call the "Project" > "Connect to selected target devices" menu
(online mode).
2. Call the "Target system > Load > Load CPU/drive unit to tar-
get device..." menu.
1. Select the drive unit in the project tree.
2. Call the "Target system > Copy RAM to ROM" menu
(save the data on the memory card).
Commissioning
Comment
The drive data can be
copied to the clipboard for
plant documentation pur-
poses and then added to a
text program, for example.
-
-
-
The line contactor should
be controlled from the drive
object (DO) Infeed_1.
See function diagram
[8838]
In the "Function > Line
contactor control" screen
form, you can check that
the interconnection is cor-
rect.
Left-click the drive unit
(SINAMICS S120).
131