Mitsubishi Electric Q26UD(E)HCPU User Manual page 372

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[LINK PARA. ERROR]
• CC-Link module whose station type is set to
"master station (compatible with redundant
function)" is mounted on the extension base unit
in the redundant system.
• CC-Link module whose station type is set to
3105
"master station (extension base)" is mounted on
the main base unit in the redundant system.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
The CC-Link link refresh range exceeded the file
register capacity.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN/When an
END instruction or a COM instruction executed
[LINK PARA. ERROR]
The network refresh parameter for CC-Link is out
of range.
■Collateral information
• Common information: File name
3106
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN/When an
END instruction or a COM instruction executed
[LINK PARA. ERROR]
The setting of the network refresh range crosses
over the boundary between the internal user
device and the extended data register (D) or
extended link register (W).
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
• The CC-Link parameter setting is incorrect.
• The set mode is not allowed for the version of
the mounted CC-Link module.
3107
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
• When the CC-Link IE Field Network is used, the
network number set in "Network Parameter" and
"Switch Setting" is duplicated.
• No "Network Parameter" and "Switch Setting"
are configured, or the CC-Link IE Field Network
3150
module with an incorrect switch setting is
mounted.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset
370
Corrective action
• Correct and write the network parameters.
• If an error occurs again even after it is
corrected, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
Change the file register file for the one that
the entire target range can be refreshed.
Check the parameter setting.
Set the network refresh range so that it does
not cross over the boundary between the
internal user device and the extended data
register (D) or extended link register (W).
Check the parameter setting.
• Check the parameter setting.
• Configure "Network Parameter" and
"Switch Setting", and then write network
parameters and the switch setting to the
module.
LED status,
Corresponding
CPU status
RUN: Off
ERR.:Flashing
QnPRH
CPU Status:Stop
Qn(H)
QnPH
QnPRH
LCPU
RUN: Off
QCPU
ERR.:Flashing
LCPU
CPU Status:Stop
LCPU
RUN: Off
ERR.:Flashing
QCPU
LCPU
CPU Status:Stop
RUN: Off
ERR.:Flashing
LCPU
CPU Status:Stop
CPU
QnU
QnU
QnU

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents