Settings - Toshiba GRE110 Instruction Manual

Overcurrent protection relay
Table of Contents

Advertisement

2.1.4 Settings

The table shows the setting elements necessary for the phase and residual overcurrent protection
and their setting ranges.
Element
Range
OCCT
1 - 20000
EFCT
1 - 20000
OC1
0.10 – 25.00 A
TOC1
0.010 – 1.500
0.00 – 300.00 s
TOC1R
0.0 – 300.0 s
TOC1RM
0.010 – 1.500
EF1
0.05 – 25.00 A
TEF1
0.010 – 1.500
0.00 – 300.00 s
TEF1R
0.0 – 300.0 s
TEF1RM
0.010 – 1.500
[OC1EN]
Off / On
[MOC1]
D / IEC / IEEE / US / C
[MOC1C]
MOC1C-IEC
NI / VI / EI / LTI
MOC1C-IEEE
MI / VI / EI
MOC1C-US
CO2 / CO8
[OC1R]
DEF / DEP
[OC1-2F]
NA / Block
[EF1EN]
Off / On
[MEF1]
D / IEC / IEEE / US / C
[MEF1C]
MEF1C-IEC
NI / VI / EI / LTI
MEF1C-IEEE
MI / VI / EI
MEF1C-US
CO2 / CO8
[EF1R]
DEF / DEP
[EF1-2F]
NA / Block
Step
Default
Remarks
1
400
CT ratio for 3-phase current
1
200
CT ratio for earth-fault curret
0.01 A
1.00 A
OC1 threshold setting
0.001
1.000
OC1 time multiplier setting. Required if [MOC1] =
IEC, IEEE, US or C.
0.01 s
1.00 s
OC1 definite time setting. Required if [MOC1] =
DT.
0.1 s
0.0 s
OC1 definite time delayed reset. Required if
[MOC1] = IEC or if [OC1R] = DEF.
0.001
1.000
OC1 dependent time delayed reset time multiplier.
Required if [OC1R] = DEP.
0.01 A
0.30 A
EF1 threshold setting
0.001
1.000
EF1 time multiplier setting. Required if [MEF1] =
IEC, IEEE, US or C.
0.01 s
1.00 s
EF1 definite time setting. Required if [MEF1] =DT.
0.1 s
0.0 s
EF1 definite time delayed reset. Required if
[MEF1] = IEC or if [EF1R] = DEF.
0.001
1.000
EF1 dependent time delayed reset time multiplier.
Required if [EF1R] = DEP.
On
OC1 Enable
D
OC1 characteristic
OC1 inverse curve type.
NI
Required if [MOC1] = IEC.
MI
Required if [MOC1] = IEEE.
CO2
Required if [MOC1] = US.
DEF
OC1 reset characteristic. Required if [MOC1] =
IEEE or US.
NA
OC1 2f block Enable
On
EF1 Enable
D
EF1 characteristic
EF1 inverse curve type.
NI
Required if [MEF1] = IEC.
MI
Required if [MEF1] = IEEE.
CO2
Required if [MEF1] = US.
DEF
EF1 reset characteristic. Required if [MEF1] =
IEEE or US.
NA
EF1 2f block Enable
 14 