CHAPTER 7: COMMISSIONING
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Compare this time to the
OVERFREQUENCY DELAY
Provided that the operate times are not scattered over a wide range, it may be desirable to
repeat this test several times and average the results.
If there is a wide scatter, verify the test setup and ensure the signal source behaves in a
consistent manner.
Current input function (voltage input disabled):
If the voltage input is disabled, the frequency elements use the winding 1 phase A current
signal as a source. Verify the operation of the element using the procedure below.
Using the variable-frequency current source connected to terminals H1
and G1, no voltage connections, frequency at 60.00 Hz (or 50.00 Hz),
and the amplitude to rated CT secondary current.
Monitor the appropriate trip and auxiliary relays.
Reset all relay alarms and indications.
The relay display should remain unchanged with no trip indications.
Slowly increase the frequency until the output relay(s) operate.
Check that the frequency at which operation took place is the selected
frequency setting.
Slowly reduce the current.
Note the current at which the output relay(s) reset.
Check that this dropout current is the minimum operating current
selected in the settings.
If current sensing has been disabled for this element, then operation
continues down to 0.00 A.
Increase the current back to nominal.
Check that the relay(s) operate.
Check that the Trip and Pickup LEDs are on and one of the following
trip messages is displayed:
LATCHED: Overfrequency or OPERATED: Overfrequency
Slowly decrease the frequency until the Pickup LED turns on and output
relays reset.
Note the dropout level, which should be the pickup minus 0.03 Hz.
Check that the Trip LED is still on.
The trip message stays on if the
Latched; if it is Self-resetting, the message resets when frequency is
below the setpoint.
For timing tests, the signal generator must be capable of triggering into
step-wise changing of frequency or ramping down to a pre-selected
frequency in only a few milliseconds.
Connect the signal source and timer start triggers as shown in FIGURE
7–12: Frequency element testing on page 7–44.
PROTECTION SCHEMES
S4 ELEMENTS
FREQUENCY
setting.
OVERFREQUENCY TARGET
setting is
7–49