ADEMCO VISTA-20P Installation And Setup Manual
Hide thumbs Also See for VISTA-20P:
Table of Contents

Advertisement

K5305-1V1 8/01
9,67$39,67$3&1
9,67$39,67$3&1
,QVWDOODWLRQDQG6HW8S*XLGH
AR ME
D
RE AD Y
OFF
ON
6HFXULW\6\VWHPV
®

Advertisement

Table of Contents
loading

Summary of Contents for ADEMCO VISTA-20P

  • Page 1 9,67$39,67$3&1 9,67$39,67$3&1 6HFXULW\6\VWHPV ,QVWDOODWLRQDQG6HW8S*XLGH AR ME RE AD Y ® K5305-1V1 8/01...
  • Page 2: Recommendations For Proper Protection

    RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
  • Page 3: Table Of Contents

    Table Of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Section 1.
  • Page 4 About Schedules ................................10-1 Section 11. System Communication......................11-1 Panel Communication with Central Station ......................... 11-1 Report Code Formats ..............................11-1 Ademco Contact ID ® ............................... 11-2 Section 12. System Operation........................12-1 Security Codes................................. 12-1 Keypad Functions ................................12-2 Various System Trouble Displays ..........................12-3 Section 13.
  • Page 5: Section 1. Features And Installation Highlights

    • Paging feature allows certain system conditions to be reported to pager phone numbers; can use a dedicated key on keypads to send a signal to a pager (VISTA-20P = 4 pagers; VISTA-15P = 2 pagers) • Built-in Telephone Line Monitoring option can monitor the telephone line voltage and can cause a local display, or a display and trouble/alarm sound.
  • Page 6: Compatible Devices

    • Supports up to 8 Addressable Keypads: Fixed-Word Display Keypad (6150), Alpha Keypad (6160) • Supports 4219, 4229 addressable hardwire zone expander modules (VISTA-20P = up to five for up to 40 expansion zones; VISTA-15P = up to 2 for up to 16 expansion zones) •...
  • Page 7: Section 2. Mounting And Wiring The Control

    S E C T I O N Mounting and Wiring the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring this control and its peripheral devices.
  • Page 8: Mounting Board With Rf Receiver

    Installation Instructions Notes Mounting Board with RF Receiver • Do not mount the cabinet on or near metal a. Remove the receiver board from its case, then objects. This will decrease RF range and/or block insert the top of the board into the slots at the top RF transmissions from wireless transmitters.
  • Page 9: Wiring To Keypads

    Mounting and Wiring the Control Notes Wiring to Keypads • Typical Fixed-Word Display: 6150 Connect keypads to the control’s keypad terminals as • Typical Alpha Display: 6160 shown on the Summary of Connections diagram. • The system supports up to 8 keypads, which can Determine wire gauge using the Wiring Run Chart be assigned to partitions in any combination below.
  • Page 10: Sounder (Bell) Connections

    Installation Instructions Sounder (Bell) Connections Notes This control complies with NFPA requirements for 1. Make sounder connections to alarm output terminals temporal pulse sounding of fire notification appliances. 3 (+) and 4 (–). Temporal pulse sounding for a fire alarm consists of: For supervised output, continue with steps 2 and 3.
  • Page 11: Backup Battery

    NP4-12 (two) ‡ 500mA 17.2AH NPG18-12 ‡ NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will fit inside the panel’s cabinet.) Notes Earth Ground • This product has been designed and laboratory-...
  • Page 12: Hardwire Zones

    Normally Closed Zones 1. Connect closed circuit devices in series in the high (+) Zone Doubling (VISTA-20P only): side of the loop, with the EOLR connected in series This feature provides two hardwired zones for each following the last device.
  • Page 13: 4219/4229 Expansion Zones

    4219/4229 Zone Expander Modules as follows: terminals. 2. Assign each module a unique device address using its VISTA-20P: Up to 40 expansion zones using up DIP switches. Zone numbers are based on the device to five Zone Expander Modules. addresses listed in the table below.
  • Page 14: Installing The Rf Receiver

    RF signals from at least one 5881M/5882M up to 16 supervised transmitter are received within 12 5881H/5882H VISTA-20P = up to 40 hours. VISTA-15P = up to 26 If the receiver is mounted remotely: 1. Set Device Address to “00” as described in its •...
  • Page 15: Installing A Keyswitch

    Zone Type 05 – Trouble by Day / Alarm by Night. EOLR (use appropriate value) • a fire alarm installation, the keyswitch must be located next to an alphanumeric display keypad. TRIGCON-004-V0 Figure 10. Keyswitch Wiring Connections The Ademco 4146 keyswitch is UL Listed.
  • Page 16: Connecting Relay Modules

    2 no. 2 (zn 17-24) no. 3 † no. 3 † (zn 25-32) no. 4 † no. 4 † (zn 33-40) no. 5 † (zn 41-48) † Applies to VISTA-20P only. 4204 RELAY 4 4204 TYPICAL (SHOWN "OFF") DIP SWITCH...
  • Page 17: Powerline Carrier Devices

    4300 or 1321X10 Transformer instead of instructions included with each. the 1321 Transformer. VISTA-20P: Up to 16 devices (if no relays are used) VISTA-15P: Up to 8 devices (if no relays are used) • The 4300/1321X10 Transformer provides AC power to the control panel, and also supplies 2.
  • Page 18: Phone Line/Phone Module Connections

    Installation Instructions Notes Phone Line/Phone Module Connections • Use 4285 or 4286 Phone Modules. 1. Connect incoming phone line and handset wiring to Compatibility: 4286 Phone Modules must have the main terminal block (via an RJ31X jack) as software version WA4286-15.1 or higher (refer to shown in the Summary of Connections diagram at the label on the square 4286 microprocessor chip).
  • Page 19: Long Range Radio Connections

    Mounting and Wiring the Control Notes Long Range Radio Connections • Use compatible Long Range Radios (e.g., Connect the data in/data out terminals and voltage 7720PLUS, 7820, 7835C, or 7845C). input terminals of the Long Range Radio to the control's keypad connection points. Set the radio’s address to “03”...
  • Page 20 Installation Instructions 2-14...
  • Page 21: Section 3. Programming Overview

    *58 Expert Programming mode. Refer to those sections for detailed procedures. The VISTA-20P system can control two independent areas of protection (known as partitions) for use by independent users, if desired, by simply assigning zones to one or the other partition during zone programming.
  • Page 22: Keypads

    † These fields must be enabled for Residential Fire and UL Residential Burglar Alarm installations. Pager Programming The system can send various reports to several pagers (VISTA-20P = up to 4; VISTA-15P = up to 2). To program pager reporting, do the following: 1.
  • Page 23: Function Keys

    Function Keys To assign functions to the function keys, use *57 Function Key menu mode. To assign emergency key functions (function key option “00”), first program the respective emergency zone number (95 for “A” key, 96 for “C” key, 99 for “B” key) with the desired zone type using *56 Zone Programming mode, then use *57 Function Key menu mode to assign the desired key.
  • Page 24 Installation Instructions • Usually assigned to a zone containing an emergency button. Type 06 • Sends a report to the central station but provides no keypad display or sounding. 24-hour Silent Alarm • Assign to a zone that has an emergency button. Type 07 •...
  • Page 25: Mechanics Of Programming

    • Usually assigned to all sensors or contacts on exterior doors and windows where Type 24 Silent Burglary bells and/or sirens are NOT desired. • Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the zone is faulted when the system is armed in the Away, Stay, or Instant, modes.
  • Page 26 5800TM Module automatic † 4219/4229 addresses 9-11 and 4204 addresses 14-15 apply to the VISTA-20P only. †† Addressable devices are identified by “1” plus the device address when reporting. Enter a report code for zone 91 to enable addressable device reporting (default = reports enabled). See field *199...
  • Page 27: Section 4. Data Field Programming

    S E C T I O N Data Field Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order.
  • Page 28: Zone Sounds & Timing ( ∗ 31- ∗ 39)

    Installation Instructions FIELD TITLE and DATA ENTRIES EXPLANATION If selected, all messages programmed to go to the primary telephone Long Range Radio Output line receiver will also be sent to the connected 7720PLUS, 7820, 0 = not used 7835, or 7845 Radio (sent in Contact ID format). The data line is 1 = using Long Range Radio output supervised as well as certain functions in the radio.
  • Page 29: Dialer Programming ( ∗ 40 - ∗ 50)

    2 = Pulse Dial; 3 = Tone Dial Select report format for primary and secondary phone numbers. Report Format (Primary/Secondary) 0 = 3+1, 4+1 ADEMCO L/S STANDARD 1 = 3+1, 4+1 RADIONICS STANDARD 2 = 4+2 ADEMCO L/S STANDARD 3 = 4+2 RADIONICS STANDARD 6 = 4+2 ADEMCO EXPRESS 7 = ADEMCO CONTACT ID®...
  • Page 30 ADEMCO Contact ID® Reporting: Enter a digit in the first box to enable the zone to report. Use a different digit for each zone until you have used up available digits. If the number of zones exceeds the number of available digits, begin with digit 1 again.
  • Page 31 FIELD TITLE and DATA ENTRIES EXPLANATION Trouble Report Code This will be sent if a zone has a trouble condition. UL: Required for UL commercial burglar alarm installations and 0 = no report required for residential fire alarm installations. 1st digit non-zero = send report Bypass Report Code This will be sent when a zone is manually bypassed.
  • Page 32: Miscellaneous System Fields

    This system has the ability to record various events in a history log Event Logging (VISTA-20P = 100 events; VISTA-15P = 50 events). At any time, the 0 = no event logging downloader operator can then upload the log and view or print out all 1 = log Alarm/Alarm Restore or selected categories of the log.
  • Page 33 FIELD TITLE and DATA ENTRIES EXPLANATION Select the desired options by adding the values of each desired option. Option Selection Multiple choice example: for both AAV and Exit delay restart†, enter 0 = none # + 12 (4 + 8). 4 = using Audio Alarm Verification (AAV) unit 8 = Enable Exit delay restart ††...
  • Page 34: Pager Programming Fields

    Installation Instructions Pager Programming Fields FIELD TITLE and DATA ENTRIES EXPLANATION Pager 1 Phone No. If you enter fewer than 20 digits, exit by pressing [∗] and next field *160 number. To clear entries from this field, press ∗160∗. Enter up to 20 digits Up to 16 optional characters may be sent as a prefix to the 7-digit Pager 1 Characters *161...
  • Page 35: Miscellaneous System Fields

    FIELD TITLE and DATA ENTRIES EXPLANATION Pager 3 Phone No. VISTA-20P only. *166 If you enter fewer than 20 digits, exit by pressing [∗] and next field Enter up to 20 digits number. To clear entries from this field, press ∗166∗.
  • Page 36: Configurable Zone Type Programming Fields

    Installation Instructions Configurable Zone Type Programming Fields The system allows you to define custom zone types (VISTA-20P supports 4 [types 90-93]; VISTA-15P supports 2 [types 90, 91]), based on the options described below. All configurable zone types can be programmed via the downloader. Configurable zone types 90 and 91 can also be programmed from a keypad using data fields *182-*185 described below.
  • Page 37 Configurable Zone Type Charts ENTRY 1 ENTRY 2 Response when system disarmed and zone is: Auto Restore Vent Zone Intact EOL Open Shorted RF zone normal RF zone N/A RF zn off-normal INTACT OPEN SHORTED 0 = normal 0 = normal 0 = normal 0 = no 0 = no...
  • Page 38: Keypad Programming Fields

    EXPLANATION Keypad 2 Keypad Device Address 17 *190 First digit: For VISTA-20P, enter the partition in which the keypad 1st Digit – Partition Assignment: is located; for VISTA-15P, enter 1 to enable, or 0 to disable. 0 = keypad disabled...
  • Page 39: Section 5. Zone Programming

    Enter the zone number that you wish to program. Zone 10 has been Zone Number Enter Zn Num. entered as an example in the display at left. VISTA-20P: 01-64 (00 = Quit) Enter a report code for zone 91 to enable addressable device VISTA-15P: 01-06, 09-34, 49-56 reporting.
  • Page 40: Installation Instructions

    Zone 1 is automatically set for EOL operation. † 1 = NC 4 = double-balanced 2 = NO † VISTA-20P only [ ∗ ] to continue Response Time (RT) This prompt appears only for hard-wired zones 01-08 (zone 02 is used 02 Response Time as an example in display).
  • Page 41 PROMPT VALID ENTRIES EXPLANATION Used only when enrolling wireless transmitters. Serial number Entry and 10 INPUT S/N: a. Transmit two open/close sequences. If using a button-type Loop Number Entry A 0 2 2 - 4 0 6 4 transmitter, press and release the button twice, but wait about 4 see explanation seconds before pressing the button the second time.
  • Page 42: Completing Zone Programming

    (zone number, zone type, loop number, etc.) relevant to that device. ∗58 Expert Programming Mode Procedures This method is designed for use by installers with previous experience in programming ADEMCO control panels. This mode is also used to program wireless keys using pre-defined templates.
  • Page 43 PROMPT VALID ENTRIES EXPLANATION Manually enter the serial number (found on the transmitter label), Serial number 10 INPUT S/N: by typing digits in the “X” locations, using the [A] (advance) or [B] S/N = serial number A X X X - X X X –...
  • Page 44: To Enter And Duplicate Wireless Keys

    Installation Instructions To Enter and Duplicate Wireless Keys This procedure programs the wireless keys, but a key is not active until it is assigned to a user number (see System Operation section, assigning attributes command). If the D key was previously pressed (from *58 Menu mode) to enter and duplicate 5804 and/or 5804BD wireless keys, the following screens appear.
  • Page 45 If the serial number transmitted does not match the serial number Not Confirmed Entd A022-4063 entered, a display similar to the one shown will appear. If the loop [ ∗ ] to continue Rcvd A022-4064 number does not match, it will also be displayed. If so, activate the button on the wireless key once again.
  • Page 46 Installation Instructions...
  • Page 47: Section 6. Output Device Programming

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Output Device Programming Output Devices: The VISTA-20P system supports up to 16 relays and/or Powerline Carrier devices (X-10 devices) plus 2 built-in trigger outputs in any combination. These 18 “outputs” are assigned to system-wide output numbers (01-18). Use *79 Menu Mode to assign output numbers and map them to device addresses.
  • Page 48 This is the logical (or reference) relay number as used in the system. ENTER OUTPUT NO. Relays and X-10 devices are numbered 01-16; the on-board triggers 01-16 = VISTA-20P relays/X-10 00 = QUIT are numbered 17 and 18 and are factory set. Use the worksheet on...
  • Page 49: *80 Menu Mode: Defining Output Functions

    *80 Menu Mode: Defining Output Functions Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components: Output Definition Components Component...
  • Page 50 Installation Instructions Activated By Select where the initiating event for this output definition is to occur 01 Activated By: as follows: 0 = delete Zone List 0 = delete (deletes the output function and any previous 1 = zone list 2 = zone type programming;-see prompt below) 3 = zone number...
  • Page 51 Enter the device output number (programmed in *79 Menu Mode) Output Number Enter Output No. you want associated with this output. 01-16 = VISTA-20P output no. Press [ ✱ ] to continue. 01-08 = VISTA-15P output no. 17-18 = on-board triggers A summary screen appears showing the programmed settings.
  • Page 52 Installation Instructions...
  • Page 53: Section 7. Zone Lists ( 81 Menu Mode)

    6, 7, 8 general purpose zones that activate pager 1 zones that activate pager 2 zones that activate pager 3 (VISTA-20P only) zones that activate pager 4 (VISTA-20P only) Zone List Programming Zone List programming involves: 1. Selecting an appropriate zone list number;...
  • Page 54 Installation Instructions Notes: • Any list may include any or all of the system's zone numbers. • A zone list can be assigned to more than one output relay. • When creating zone list 4 for cross zoning, include only zones assigned to zone types 3, 4, or 5. Do not include zones that have delays (entry/exit zones, interior w/delay) or 24-hour zones, as these zone types may produce unpredictable operation and may not function as intended.
  • Page 55: Section 8. Function Key Programming (∗57 Menu Mode)

    Arm STAY (reports as User 00 if closing reports are enabled) †† Macros 11-12 apply to 05 = Arm NIGHT-STAY (reports as User 00 if closing reports enabled) VISTA-20P only. 06 = Step Arming (arms STAY, then NIGHT-STAY, then AWAY) 07 = Device A ctivation (for device programmed as system operation type 66–function key in *80 Menu Mode)
  • Page 56 Installation Instructions...
  • Page 57: Section 9. Alpha Descriptor Programming (*82 Menu Mode)

    S E C T I O N Alpha Descriptor Programming (*82 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Descriptor Programming The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults.
  • Page 58 Installation Instructions To delete or change the default descriptor for zone 1, press [ ✱ ] plus Flashing Cursor ✱ Z N 0 1 the same zone number (01). This will clear that descriptor and allow changes to be made at the flashing cursor. [∗] to continue NOTE: If you do not wish to change the existing descriptor for zone 1, enter [ ✱...
  • Page 59: Adding Custom Words (Will Not Be Annunciated By 4285/4286 Phone Module)

    VISTA-15P: You can create a custom message display that appears on alpha keypads instead of “System Ready.” To assign a custom message, use word number 11 as described below. VISTA-20P: You can assign a partition descriptor (up to 16 characters) for each partition plus the common lobby.
  • Page 60 ALPHA VOCABULARY LIST (For Entering Zone Descriptors) (Word Space) LOCK SHOCK • 226 LOOP • 170 SHOP • 065 EAST • 227 SHORT ELECTRIC • 001 • 228 • 118 LOWER • 173 SIDE EMERGENCY • 002 ALARM • 229 SKYLIGHT ENTRY ALLEY...
  • Page 61: Section 10. Creating Schedules

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Schedules The VISTA-20P system provides up to 32 schedules (VISTA-15P supports 8), which can be used to control 11 types of system events at pre-defined times. Sixteen schedules are intended for use by the end-user, and sixteen are reserved for the installer (VISTA-15P = 4 user schedules, 4 installer schedules).
  • Page 62 Installation Instructions Enter the event’s start time and days of the week to occur. Start Time S T A R T S M T W T F S To select days, position the cursor under the desired days using the 01-12 = hour 0 0 1 0 0 0 0 H H M M A M...
  • Page 63: Panel Communication With Central Station

    3 (or 4) times and is followed by the second digit. This is the “expanded” digit. 4+2 Format Comprises a 4-digit subscriber number and 2-digit report code. ADEMCO Contact ID Comprises a 4-digit subscriber number, 1-digit event qualifier (“new” or Reporting Format “restore”), 3-digit event code, and 3-digit zone number, user number, or system status number (see the following page).
  • Page 64: Ademco Contact Id

    Duress = 92 3 + #, or C = 96 Tamper = 9 ® Ademco Contact ID ® The Ademco Contact ID Reporting Format comprises the following: 4-digit subscriber number. 1-digit event qualifier (“new” or “restore”). 3-digit event code. 2-digit Partition No.
  • Page 65 ® Ademco Contact ID Reporting takes the following format: CCCC Q EEE GG ZZZ where: CCCC = Customer (subscriber) ID Q = Event qualifier, where: E = new event , and R = restore EEE = Event code (3 hexadecimal digits) Note: For a complete list of event codes, refer to the central office receiver manual.
  • Page 67: Section 12. System Operation

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Security Codes The VISTA-20P system supports up to 48 security codes (VISTA-15P supports 32 codes), which can each be assigned one of 5 authority levels. The authority level determines the functions each code...
  • Page 68: Keypad Functions

    Installation Instructions Keypad Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual. Function Description Silence alarms Pressing any key will silence the keypad sounder for 10 seconds. Disarming the system will silence both keypad and external sounders.
  • Page 69: Various System Trouble Displays

    Panic Keys There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a report to the central station. Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal Emergency responses.
  • Page 70 Installation Instructions Alpha Display Fixed Disp. Meaning Modem Comm The system is in communication with the central station for change of function or status verification. no display no display Power Failure If there is no keypad display at all and the LEDs are unlit, operating power (AC and battery) for the system has stopped and the system is inoperative.
  • Page 71: Section 13. Testing The System

    S E C T I O N Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Test Procedures After the installation is complete, you should perform the following tests: System Test:...
  • Page 72: Go/No Go Test Mode

    Installation Instructions Checking Transmitter Enrollment (Sniffer Mode) Use this mode to verify that all transmitters have been properly programmed. Make sure both partitions are disarmed before trying to enter this mode, since this is a system-wide command. 1. Press [Installer code] + [#] + 3. Note: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer mode.
  • Page 73: Dialer Communication Test

    Dialer Communication Test 1. Enter Installer Code + 5 [ TEST ], then press “1” at the prompt to start the Dialer Test. 1=DIAL, 0=WALK The following will be displayed (accompanied by 2 beeps) if test is successful: PHONE OKAY (“Cd”...
  • Page 74 Installation Instructions 13-4...
  • Page 75: Section 14. Specifications & Accessories

    1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No. 1321 (in U.S.A.) RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type). Charging Voltage: 13.8VDC.
  • Page 76 1321: 16.5VAC, 25VA Plug-In Transformer (No. 1321CN in Canada) Transformers: 1321X10: Powerline Carrier device Interface AC Transformer 4300: Powerline Carrier device Interface AC Transformer Ademco AB-12M 10” Motorized Bell & Box Sounders: Ademco 1011BE12M 10” Motorized Bell & Box Ademco 702 Outdoor Siren...
  • Page 77: 5800 Series Transmitter Input Loop Identification

    5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones). NOTE: For information on any transmitter not LOOP 3 LOOP...
  • Page 78 Installation Instructions Compatible 5800 Series Transmitters Table (continued) Model Product Input Type Description Has three unique input (loop) codes: one for a “Primary” contact 5817 Multi-Point Universal loop with programmable options; the others for two “auxiliary” Transmitter closed circuit contact loops. •...
  • Page 79: Section 15. Regulatory Agency Statements

    S E C T I O N Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • RADIO FREQUENCY EMISSIONS Federal Communications Commission (FCC) Part 15 This device complies with part 15 of the FCC rules.
  • Page 80 Installation Instructions UL NOTICES ✱ 1. Entry Delay No. 1 (field 35) cannot be greater than 45 seconds, and Entry ✱ Delay No. 2 (field 36) cannot be greater than 60 seconds for UL installations. ✱ 2. The maximum number of reports per armed period (field 93) must be set to “0”...
  • Page 81: Section 16. Limitations And Warranty

    S E C T I O N Limitations and Warranty • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against...
  • Page 82 Installation Instructions WARNING THE LIMITATIONS OF THIS ALARM SYSTEM (Continued) The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
  • Page 83 – NOTES – 16-3...
  • Page 84 Installation Instructions – NOTES – 16-4...
  • Page 85 – INDEX – 1321 AC Transformer..1-2, 2-4, 2-11 Backup Battery......iii, 1-2 Factory Defaults ....... 3-6 1321X10....1-2, 2-4, 2-11, 14-2 Battery Life........2-9 Fast Busy Signal ......2-12 15-Second Dialer Delay (Burglary) ... 4-3 Battery Tests......13-1, 13-3 Fault Delay Time ......
  • Page 86 Installation Instructions PABX Access Code ......4-2 SA4120XM-1 Trigger Cable....2-4 Wireless Key Templates ....5-6 Pager 1 Phone No..... 4-8, 4-9 Schedules ........10-1 Wiring Length/Gauge Chart....2-3 Pager Format ........4-8 Secondary Phone No....... 4-3 Wiring Run Chart......2-3 Pager Programming ....
  • Page 87 Figure 17. Summary of Connections 16-7...
  • Page 88 24 months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply.

This manual is also suitable for:

Vista-20pcnVista-15pVista-15pcn

Table of Contents