Honeywell ALL-SPEC Installation Instructions Manual page 5

Air sampling smoke detection system

Advertisement

Setting the function of the fault contact
The contact type (break contact or make contact) of the collective fault is set using the jumper JU 2 and JU 3.
Fault contact detector module I = Jumper JU2
Fault contact detector module II = Jumper JU3
The following table shows the positioning of the jumpers:
X = pin pair bridge
O = pin pair open
The standard settings have a grey background.
Setting the collective fault contact
Jumper
JU2/3
Pin No.
1+2
break contact
X
make contact
O
Device Supports
A
Support type MT-1
horizontal installation
B
Support type MT-1
vertical installation
ALL-SPEC_Unit_HON.doc
JU2/3
2+3
O
X
A
B
07/2011